• Applications
  • Features
ABL8R
POWER FACTOR CORRECTION FILTER IEC 61000-3-2
Power reserve of +50% when required
Integrated diagnostics (LED and relay)
<=30 A at 2 ms inrush current
0.51 at 240 VAC, 0.59 at 120 VAC cos phi
87 to 100% efficiency, 15.5 W power dissipation
24 to 28.8 VAC adjustable output voltage limits
1 to 3% line and load regulation
>=120 ms at 400 VAC, >=20 ms at 100 VAC, >=40 ms at 240 VAC holding time
3 x 0.5 to 3 x 4 sq-mm AWG 22 to AWG 12 screw type terminals input connection, connection capacity, 1 x 0.5 to 1 x 4 sq-mm AWG 22 to AWG 12 screw type terminals input ground connection, connection capacity, 4 x 0.5 to 4 x 4 sq-mm AWG 22 to AWG 12 screw type terminals output connection, connection capacity, 1 x 0.5 to 1 x 4 sq-mm AWG 22 to AWG 12 screw type terminals output ground connection, 2 x 2.5 sq-mm removable screw terminal block diagnostic relay, connection capacity
6561.68 ft operating altitude
Series/parallel output coupling
Class I conforming to VDE 0106-1 overvoltage category
1 LED green and red output voltage, 1 LED green, red and orange output current
0 to 90% during operation, 0 to 95% in storage relative humidity
-40 to 158 deg F storage temperature
EMC conforming to EN 61000-6-1, EMC conforming to EN 61000-6-3, EMC conforming to EN/IEC 61000-6-2, EMC conforming to EN/IEC 61000-6-4, EMC conforming to EN/IEC 61204-3, Safety conforming to EN/IEC 60950-1, Safety conforming to EN/IEC 61204-3, Safety conforming to SELV environmental characteristic
Manual or automatic reset against overload, protection technology, 30 to 32 VAC, manual reset against overvoltage, protection technology, manual or automatic reset against short-circuits, protection technology, tripping if U < 21.6 V against under voltage, protection technology, automatic reset thermal, protection technology
35 x 7.5 mm symmetrical DIN rail, 35 x 15 mm symmetrical DIN rail mounting support
Between input and ground, between output and ground, between input and output, between outputs dielectric strength
1 or 2 phase