• Applications
  • Features
ABL8R
INTEGRATED FUSE (NOT INTERCHANGEABLE)
Vertical operating position
85 to 264 VAC input voltage limits, 47 to 63 Hz network frequency
<=30 A inrush current
0.65 cos phi
>85% efficiency, 12.7 W power dissipation
0.83 A at 240 VAC, 1.46 A at 100 VAC current consumption
100 to 120% adjustable output voltage limits
+/- 3 % line and load regulation
>=10 ms at 100/240 VAC holding time
2 x 0.14 to 2 x 2.5 sq-mm AWG 26 to AWG 14 screw type terminals input connection, connection capacity, 1 x 0.14 to 1 x 2.5 sq-mm AWG 26 to AWG 14 screw type terminals input ground connection, connection capacity, 2 x 0.14 to 2 x 2.5 sq-mm AWG 26 to AWG 14 screw type terminals output connection, connection capacity, 1 x 0.14 to 1 x 2.5 sq-mm AWG 26 to AWG 14 screw type terminals output ground connection, connection capacity
6561.68 ft operating altitude
Parallel/series output coupling
Class I conforming to VDE 0106-1 overvoltage category
1 LED green output voltage, 1 LED orange input voltage status
0 to 95% without condensation or dripping water relative humidity
EMC conforming to EN 50081-1, EMC conforming to EN 50082-2, EMC conforming to EN/IEC 61000-6-2, Safety conforming to EN/IEC 60950, Safety conforming to SELV environmental characteristic
1.1 x In against overload, protection technology, tripping if U > 1.5 x Un against overvoltage, protection technology, automatic reset against short-circuits, protection technology, tripping if U < 0.8 x Un against under voltage, protection technology output protection type
35 x 15 mm symmetrical DIN rail, 35 x 7.5 mm symmetrical DIN rail, 75 x 7.5 mm symmetrical DIN rail mounting support
Between input and ground, between output and ground, between input and output, between outputs dielectric strength
1 or 2 phase