Schneider Electric TeSys™ GB2 Circuit Breaker, 250/277 VAC/48 VDC, 10 A, 1 kA, 1 Pole, Thermal Magnetic Trip
Relays
598550
MFG #: GB2CB16
Square D™
54.25000
/ ea
- Brochure URL - 115967977b38aa63fd29e8e8024eb8003e40dffe.pdf(Brochure URL)
- Computer~Aided [CAD|BIM] Model URL(Computer~Aided [CAD|BIM] Model URL)
- Seller Home Page URL - us(Seller Home Page URL)
- Spec Sheet URL - 11003_7C8JNHT9B1QMOU4L.pdf(Spec Sheet URL)
- Tech Drawing URL - 52f6d012bc55f0c10d946cd0bde3e1e1158578f9.pdf(Tech Drawing URL)
- Video - https://youtube.com/embed/TSV0sFWYLME(Video)
- Applications
- Features
Control |
SET OF 6 |
Category A conforming to IEC 60947-2, DC-12 conforming to IEC 60947-5-1, DC-13 conforming to IEC 60947-5-1 utilization category |
50/60 Hz conforming to IEC 60947-2 network frequency |
Icu = 50 kA at 230/240 VAC at 50/60 Hz, Icu = 1 kA at 48 VDC, Icu = 50 kA at 110 VAC 50/60 Hz, Icu = 1.5 kA at 24 VDC conforming to IEC 60947-2 |
50 % at 110 VAC 50/60 Hz, 25 % at 230/240 VAC 50/60 Hz conforming to IEC 60947-2 |
By clips mounting mode |
Horizontal/vertical mounting position |
Toggle control type |
277 VAC 50/60 Hz conforming to CSA C22.2 No 14, 48 VDC, 250 VAC 50/60 Hz conforming to IEC 60947-2, 277 VAC 50/60 Hz conforming to UL 1077 rated operational voltage |
4 kV conforming to IEC 60947-2 rated impulse withstand voltage |
2 W power dissipation per pole |
8000 cycles mechanical durability |
8000 cycles electrical durability |
Connector 1 cable 0.75 to 6 sq-mm, 0.75 to 4 sq-mm, 0.75 to 4 sq-mm, 0.75 to 2.5 sq-mm - cable stiffness : solid - without cable end |
1.2 N-m - on connector tightening torque |
Shocks 22 Gn for 20 ms conforming to IEC 60068-2-27, vibrations 5 Gn, 5 to 110 Hz conforming to IEC 60068-2-6 mechanical robustness |
2 9 mm pitches |
TC protective treatment |
IP20 conforming to IEC 60529 deg of protection |
-40 to 80 deg C ambient air temperature for storage |
960 deg C conforming to IEC 60695-2-1 fire resistance |