• Applications
  • Features
DISTRIBUTION
ON/OFF INDICATION
Trip free mechanism contacts cannot be held in the on position when the C60 is tripped automatically
Positive indication of contact disconnect, green mechanical indication on front face of device shows that all poles are open
Allows locking in ON-OFF position using padlock attachment
Suitable for reverse feeding
D curve - magnetic setting between 10 and 14 times ampere rating
14 to 4 AWG copper
10 kA at 120/240 VAC, 5 kA at 277 VAC, 10 kA at 60 VDC
35 mm DIN-rail mounting
Frame size C100N/63 A
IP20 conforming to IEC 60529-IP40 for modular enclosure conforming to IEC 60529