Electrical ratings: 335 AMP copper wire (Based on NEC table 310-16, 75 ° C column), CE rated voltage (Ui): 1000 VAC/VDC per IEC 60947-7-1, Rated impulse voltage (Uimp): 6000 V, Material group: IIIa, Pollution degree: 3, UL/CSA voltage rating: 600 VAC/VDC (UL 1059 class C, user group - general industrial), Factory and field wiring; Minimum enclosure size: 16 X 12 X 6 IN; Mechanical ratings: Flammability rating of insulator base: UL 94V-0 (Restricted wire rage); Tin plated aluminum and nickel plated steel terminal set screws; Zinc plated steel connector mounting screw; Panel mountable: 1/4 IN (M6) fasteners, torque to 30 - 40 LB-IN |
6 AWG to 400 kcmil (185 to 16 sq-mm) and 14 AWG to 3/0 (70 to 2.5 sq-mm) line wire range |
(8) #2 to 14 AWG (35 to 2.5 sq-mm) load wire range |
600 V per UL 1059 & CSA 22.2 no 158, class B/C requirements |
1000 VAC/VDC per IEC 60947-7-1 (CE) |
CU9 - 90 deg C connector terminal rating with copper or wire |
Factory and field-wiring |
V-0 flammability rating of insulator base per UL94 |
-40 to 125 deg C insulator base temperature |
Copper, tin plated connector |
Aluminum, tin plated line terminal set screws |
Steel, nickel-plated line terminal set screws |
Zinc plated steel connector mounting screws |
42.4 nm for 400 kcmil to 2/0 AWG/1/0 to 2 AWG/4 to 6 AWG, 13.6 nm for 3/0 AWG/2/0 to 1 AWG, 9 nm for 2 to 6 AWG, 4.5 nm for 8 AWG/10 to 14 AWG torque rating |
1-7/16 in and 1 in L wire strip for line terminal |
400 to 300 kcmil and 3/0 to 4 AWG IP20 protection for line terminal |
8 mm and 6 mm hex terminal screw drive for line terminal |
400 kcmil to 6 AWG, 3/0 to 14 AWG line terminals |
9 nm for 2 to 4 AWG/6 AWG, 4.5 nm for 8 AWG/10 to 14 AWG torque rating |
5/8 in L wire strip for load terminal |
2 to 12 AWG IP20 protection for load termina |