• Applications
  • Features
General Purpose
Fast-Acting
Used as supplementary protection in appliance or utilization equipment to provide individual protection for components or internal circuits
0.0199 ohms resistance
302.836 I2T (A2 sec) nominal melting
-55 to 125 deg C operating temperature
4 hrs minimum at 100%, 1 hr maximum at 135%, 2 min maximum at 200%
Nickel-plated brass cap, tin plated copper leads
10 kA at 125 VAC interrupting rating