Hubbell Wiring Device-Kellems HCI HBL3771 LKG RCPT, 50A 250VDC/60
Locking Devices
26615
MFG #: HBL3771
Hubbell Wiring Device-Kellems
224.57000
/ ea
- Catalog URL - Wiring_Device_Kellems_HBL2830SW_Catalog.pdf(Catalog URL)
- http://www.hubbell-wiring.com/(Seller Home Page URL)
- Install Instructions 1 URL - 11456_HKLOA502Z9YDCITF.pdf(Install Instructions 1 URL)
- Install Instructions 1 URL - WIRING_PD1344_PD1346_INSTALLINST.pdf(Install Instructions 1 URL)
- Install Instructions URL - IDW_DOCUMENT_1537662532134.pdf(Install Instructions URL)
- Line Drawing URL - 11456_NYETCAIXR90BF3KP.pdf(Line Drawing URL)
- Line Drawing URL - WDK_HBL3771_DRAWING_PDF.pdf(Line Drawing URL)
- Spec Sheet URL - 11456_0W5JU9AKTDIQ67BM.pdf(Spec Sheet URL)
- Spec Sheet URL - WIRING_HBL3771_spec.pdf(Spec Sheet URL)
- Tech Drawing URL - IDW_DOCUMENT_1537663245520.pdf(Tech Drawing URL)
- Tech Drawing URL - WIRING_HBL3771_M8310_ACAD_DRAWING.dwg(Tech Drawing URL)
- Video - https://www.youtube.com/embed/cXi_GcGBWpc(Video)
- Warranty URL - Wiring_WDK_Warranty.pdf(Warranty URL)
- Warranty URL - 11456_Y8PS6T0FNOGH3Q75.pdf(Warranty URL)
- Applications
- Features
Heavy Duty Industrial |
Standard |
Thermoset construction offers high heat resistance |
Armored housing provides superior impact resistance |
One piece contacts provide low operating temperatures |
3-wire grounding |
Zinc plate 0.062 in steel casing material |
0.05 in steel terminal |
Zinc plate steel pressure screw material |
0.062 in steel, zinc plate bridge mounting strap |
Brass rivet |
Black thermoset base |
0.04 in brass ground contact |
Zinc plated steel mounting screws |
0.1/0.04 in brass contact spring |
Black thermoset body contact carrier |
10 to 6 AWG terminal accommodation |
2000 VAC minimum dielectric voltage withstand |
Certified for current interrupting at full rated current |
Maximum 30 deg C temperature rise at full rated current after 50 cycles of overload at 150% of rated current at a power factor of 0.75 |
Terminals identified in accordance with UL 498 (x, y, z, white, green) terminal identification |
V2 or better per UL94/CSA 22.2 No 0.17 flammability |