PVC with sun resistance jacket |
Ripcord and sequential footage marking |
Aluminum mylar overall shield |
0.008 in insulation thickness |
0.062 in nominal insulated nominal conductor diameter |
4 in nominal lay length |
24 AWG tinned copper drain |
0.014 in insulation thickness |
26.5 lb/1000 ft nominal approximate cable weight |
59 pF/ft nominal capacitance between conductors at 1 kHz |
109 pF/ft nominal capacitance between conductors to shield at 1 kHz |
6.29 Ohm/1000 ft nominal DC resistance per conductor at 20 deg C |
Black, red, white insulation colors |
This cable consists of three bare copper insulated conductors with an overall shield with a drain |
The overall assembly has an overall jacket |
Class 3 power limited circuit and communication cable for riser or non-riser applications |
UL 1666 riser flame test rating |