Ind Facilities & Factories - Facility: Safety and Security Systems
Non-indicating
Time delay coupled with class CC current- limiting response provides close sizing on small motor and relay circuits and maximum component short circuit current rating protection
200 ka interrupt rating provides high ratings for control circuit locations
Class CC rejection feature, with appropriate fuse block, prevents inserting lesser rated supplementary fuse
Selective co-ordination ratio of 2:1 (within Low-Peak® fuse family) prevents electrical shutdowns from extending beyond the failed circuit
200 kA at 600 VAC (RMS symmetrical), 20 kA at 150 VDC (DC UL198L) interrupt rating
120 s at 200% of ampere rating response time
A superior, all purpose, space saving branch circuit fuse that meets most protection requirements up to 30 A
Very compact, with a physical size only 13/32 x 1-1/2 in with rejection tip
Proper sizing can provide "no damage" type 2 coordinated protection for NEMA and IEC motor controllers
Can be used where either a time delay or a fast acting fuse is needed, making selection easier and reducing spare fuse inventories for substantial cost reduction
Superior protection for small horsepower motor circuit
12 s (minimum) at 200% of rated current response time
200 kA at 600 VAC RMS symmetrical, 20 kA at 150 VDC (UL 198L) interrupt rating