Schneider Electric TeSys™ F LC1F IEC Contactor With Coil, 120 VAC Coil, 250 A Max Load, 3NO, 3 Poles
NEMA & IEC Contactors
31989
MFG #: LC1F150G6
Schneider Electric
848.10000
/ ea
- ARRA Compliant: N
- Buy American Compliant: N
- Catalog Number: LC1F150G6
- Coil Power Rating: 100 kW
- Connection Type: Bolt-On/Lug
- Contact Rating: 600 VAC, 150 A Inductive, 250 A Resistive
- Contact Type: Non-Reversing
- Country of Origin: CZ
- Dimensions: 6.69 in H x 6.44 in W x 6.73 in D
- Enclosure Type: IP20
- EU RoHS Indicator: Y
- Frequency Rating: 50/60 Hz
- Gross Weight Per Pack: 8.8600 lb
- Harmonization Tariff Schedule Code: 8536490065
- Item Group: 22336
- Mounting Type: Panel
- Operating Cycles: 10000000
- Operating Temperature: -5 to 55
- Returnable: Y
- Series: LC1F
- Terminal Type: Screw/Clamp
- UNSPSC: 39121529
- UPC 11: 78590107979
- UPC 12: 785901079798
- Wattage: 22, 8 W
- Stock Status: NORMALLY STOCKED
- Brand: Schneider Electric
- Manufacturer: Schneider Electric
- Coil Voltage: 120 VAC
- Contact Configuration: 3NO
- Maximum Load Current: 150 A Inductive, 250 A Resistive
- Type: 3-Phase
- Number Of Poles: 3
- Catalog URL - Schneider_Electric_LC1F500_Catalog.pdf(Catalog URL)
- Seller Home Page URL - us(Seller Home Page URL)
- Spec Sheet 1 URL - Schneider_Electric_LC1F150G6_Datasheet.pdf(Spec Sheet 1 URL)
- Spec Sheet URL - LC1F150G6(Spec Sheet URL)
- Tech Bulletin URL - cf57f551292bfed3bee2fd92787f7a3f0929f473.pdf(Tech Bulletin URL)
- Tech Drawing URL - d4e5fbcef7d8f2d7d2e5d36a00b59c1d76cc533c.pdf(Tech Drawing URL)
- Video - https://www.youtube.com/embed/GW6XwNd-Fek(Video)
- Features
8 kV rated impulse withstand voltage |
III overvoltage category |
250 A at <=104 deg F (40 deg C) conventional free air thermal current |
1200 A conforming to IEC 60947-4-1 rated breaking capacity |
160 A aM at <=440 V/250 A gG at <=440 V associated fuse rating |
0.35 mOhm at 50 Hz to Ith 200 A average impedance |
1000 V conforming to IEC 60947-4-1/1500 V conforming to VDE 0110 group C rated insulation voltage |
10.62 lbf-in (1.2 Nm) power circuit/159.29 lbf-in (18 Nm) tightening torque control circuit |
23 to 35 ms closing/5 to 15 ms opening operating time |
2400 cycles/hr at <=131 deg F (55 deg C) operating rate |
660 VA at 68 deg F (20 deg C) 60 Hz inrush power |
55 VA at 68 deg F (20 deg C) 60 Hz hold-in power consumption |
12 to 16 W heat dissipation |
TH protective treatment |
-40 to 158 deg F permissible ambient air temperature around the device |
9842.52 ft without derating in temperature operating altitude |
Vibrations contactor closed 6 gn, 5 to 300 Hz/shocks contactor open 9 gn for 11 ms/vibrations contactor open 2 gn, 5 to 300 Hz/shocks contactor closed 15 gn for 11 ms mechanical robustness |
65 kW at 1000 VAC 50/60 Hz AC-3, 40 kW at 220 to 230 VAC 50/60 Hz AC-3, 75 kW at 380 to 400 VAC 50/60 Hz AC-3, 90 kW at 500 VAC 50/60 Hz AC-3 motor power |
22 kW at 400 VAC 50/60 Hz AC-4, 80 kW at 415 VAC 50/60 Hz AC-3, 80 kW at 440 VAC 50/60 Hz AC-3, 100 kW at 660 to 690 VAC 50/60 Hz AC-3 motor power |
22 W (AC-1), 8 W (AC-3) power dissipation per pole |