GE LC1F115 LB1AC AC Coil, 24 VAC, 60 Hz, For Use With CL00, CL01, CL02, CL25 Contactor

NEMA & IEC Contactors
379423 MFG #: LC1F115
Schneider Electric
488.62000 / ea
  • Alternate Catalog Number: LC1F115
  • Application: Resistive load;motor control
  • ARRA Compliant: N
  • Buy American Compliant: N
  • Catalog Number: LC1F115
  • Coil Power Rating: 80 kW
  • Connection: BOLT ON OR LUGS (SOLD SEPARATELY)
  • Connection Type: Bolt-On/Lug
  • Contact Rating: 600 VAC, 115 A Inductive, 200 A Resistive
  • Contact Type: Non-Reversing
  • Country of Origin: FR
  • Currency: USD
  • Dimensions: 6.38 in H x 6.43 in W x 6.73 in D
  • Enclosure Type: IP20
  • EU RoHS Indicator: Y
  • Frequency Rating: 50/60 Hz
  • Gross Volume Per Pack: 628.32
  • Gross Volume per Pack Metric: 10296.28
  • Gross Volume UOM: CI
  • Gross Volume UOM Metric: cm3
  • Gross Weight Per Pack: 7.7800 lb
  • Gross Weight per Pack Metric: 3.52
  • Gross Weight UOM Metric: kg
  • Harmonization Tariff Schedule Code: 8536490065
  • Height: 8.58 in
  • Height [Metric]: 22.0000 cm
  • Item Group: 22336
  • Length: 9.56 in
  • Length [Metric]: 24.5000 cm
  • Material Composition Declaration: https://checkaproduct.se.com/DistantRequestDispatcher.aspx?action=export&pid=620892&lang=en-us
  • Mounting: Panel Mount
  • Mounting Type: Panel
  • Operating Cycles: 10000000
  • Operating Temperature: -5 to 55
  • Phase: 3
  • Returnable: Y
  • Series: LC1F
  • Size: 162 MM,163.5 MM,171 MM
  • Standard: UL LISTED (E164862 / NLDX) - CSA CERTIFIED (LR43364 3211 04) - IEC RATED (60647-4) - CE MARKED - ROHS COMPLIANT
  • Sub Brand: TESYS
  • Substitute Product Catalog Number: LA9FF601
  • Suitable For Use With: CL00, CL01, CL02, CL25 Contactor
  • Terminal Type: Lug
  • UNSPSC: 39121529
  • UPC 11: 78590112221
  • UPC 12: 785901122210
  • Voltage Rating: 24
  • Warranty Description: Contractual Warranty:18 months
  • Wattage: 15, 5 W
  • Width: 7.80 in
  • Width [Metric]: 20.0000 cm
  • Stock Status: NONSTOCK
  • Brand: Schneider Electric
  • Manufacturer: Schneider Electric
  • Coil Voltage: 600 VAC
  • Contact Configuration: 3NO
  • Maximum Load Current: 115 A Inductive, 200 A Resistive VAC
  • Type: 3-Phase
  • Number Of Poles: 3
QTY
  • Applications
  • Features
Resistive load;motor control
CONTACTOR ONLY (NO COIL)
8 kV rated impulse withstand voltage
III overvoltage category
200 A at 104 deg F conventional free air thermal current
920 A conforming to IEC 60947-4-1 rated breaking capacity
125 A aM at 440 V/200 A gG at 440 V associated fuse rating
0.37 MOhm at 50 Hz to Ith 200 A average impedance
1000 V conforming to IEC 60947-4-1/1500 V conforming to VDE 0110 group C rated insulation voltage
88.5 in-lb tightening torque power circuit
23 to 35 ms closing/5 to 15 ms opening operating time
2400 cycles/hr at 131 deg F operating rate
660 VA at 68 deg F 60 Hz inrush power
55 VA at 68 deg F 60 Hz hold-in power consumption
12 to 16 W heat dissipation
TH protective treatment
-40 to 158 deg F permissible ambient air temperature around the device
9842.52 ft without derating in temperature operating altitude
Vibrations contactor closed 6 gn, 5 to 300 Hz/shocks contactor open 9 gn for 11 ms/vibrations contactor open 2 gn, 5 to 300 Hz/shocks contactor closed 15 gn for 11 ms mechanical robustness
55 kW at 380 to 400 VAC 50/60 Hz AC-3, 59 kW at 415 VAC 50/60 Hz AC-3, 59 kW at 440 VAC 50/60 Hz AC-3, 75 kW at 500 VAC 50/60 Hz AC-3 motor power dissipation per pole
30 kW at 220 to 230 VAC 50/60 Hz AC-3, 65 kW at 1000 VAC 50/60 Hz AC-3, 18.5 kW at 400 VAC 50/60 Hz AC-4, 80 kW at 660 to 690 VAC 50/60 Hz AC 3-ph motor power
15 W (AC-1), 5 W (AC-3) power dissipation per pole