Square D™ EDB34080CA Type EDB Circuit Breaker, 480Y/277 VAC VAC, 80 A, 25 kA at 240 VAC/18 kA at 480Y/277 VAC Interrupt, 3 Poles, Thermal/Magnetic Trip
Lighting Panel Circuit Breakers
PDW~6399229
MFG #: EDB34080CA
Square D™
0.00000
/ ea
- Alternate Catalog Number: EDB34080CA
- Application: NF panelboard;HACR rated
- ARRA Compliant: N
- Buy American Compliant: N
- Catalog Number: EDB34080CA
- Connection: Lugs aluminium;AWG 12...AWG 2/0 aluminium;AWG 14...AWG 2/0 copper
- Connection Type: Lug
- Country of Origin: IE
- Currency: USD
- Depth: 4.05 in
- Dimensions: 5.8 in H x 2.94 in W x 4.05 in D
- EU RoHS Indicator: Y
- Frame: E
- Frequency Rating: 50/60
- Gross Weight Per Pack: 0.0159 lb
- Gross Weight per Pack Metric: 1.59
- Gross Weight UOM Metric: kg
- Harmonization Tariff Schedule Code: 8536200040
- Height: 12.1920 in
- Height [Metric]: 12.1920 cm
- Item Group: 00931
- Length: 25.1460 in
- Length [Metric]: 25.1460 cm
- Material: Thermoset Composite Resin
- Material Composition Declaration: https://checkaproduct.se.com/DistantRequestDispatcher.aspx?action=export&pid=397065&lang=en-us
- Mounting Type: Bolt-On
- Operating Temperature: 50 A°C
- Returnable: N
- Standard: cULus
- Sub Brand: EDB
- Temperature Rating: 122
- Trip Range: 1000 to 2300
- Type: Type EDB
- UNSPSC: 39121603
- UPC 11: 78590149036
- UPC 12: 785901490364
- Warranty Description: Contractual Warranty:18 months
- Width: 15.7480 in
- Width [Metric]: 15.7480 cm
- Wire Size: 12 to 2/0 AWG Al, 14 to 2/0 AWG Cu
- Brand: Square D™
- Manufacturer: Schneider Electric
- Amperage Rating: 80 A
- Interrupt Rating: 25 kA at 240 VAC/18 kA at 480Y/277 VAC
- Trip Type: Thermal Magnetic
- Voltage Rating: 480Y/277 VAC
- Number Of Poles: 3
- Install Instructions 1 URL - 11003_W405MTQD91NUXV7Z.pdf(Install Instructions 1 URL)
- Seller Home Page URL - us(Seller Home Page URL)
- Service Manual URL - 11003_6YTNP01EFUSQGWA7.pdf(Service Manual URL)
- Spec Sheet URL - 11003_5WR46TKJ32QUDAHI.pdf(Spec Sheet URL)
- Tech Drawing URL - 11003_E7QBORT8ZXCD06KA.pdf(Tech Drawing URL)
- Tech Drawing URL - 11003_QWA5EP3GZSVFI7BO.pdf(Tech Drawing URL)
- Applications
- Features
NF panelboard;HACR rated |
Trip indicator |