Weidmuller 8965370000 Signal Isolating Converter, 19.2/31.2 VDC Input, </=1.9 W, 2 Channels
Isolation Amplifiers
1214445
MFG #: 8965370000
Weidmuller
244.47000
/ ea
The ACT20X-HDI-SDO/2HDI-2SNO RNO/RNC isolating switch amplifiers are specially designed for recording NAMUR sensor signals and digital switching signals which originate from Ex zone 0. Switching relays, optionally available with NO/NC contacts, transfer output signals to the safe zone. Integrated alarm contacts issue an alert in the event of a malfunction, this makes troubleshooting easier and increases system availability. The rail mounted disconnect-switch amplifiers are optionally available in one-/two-channel versions. With 11 mm W per channel, the devices need little space in the electrical cabinet.
- Features
NAMUR sensor/switch |
Safe-output - relay |
NO contact configuration |
<20 Hz input frequency |
1 kOhm input resistance |
Output signal in case of wire break - 6.5 mA (in case of wire break) |
Input sensor supply - 8 VDC/8 mA |
Trigger level low - <1.2 mA |
Pulse duration - >0.1 ms |
Trigger level high - >2.1 mA |
Input type - intrinsically safe circuit |
Switching frequency - 0.02 kHz |
Rated switching voltage - </=250 VAC/30 VDC (safe area), </=32 VAC/32 VDC (zone 2) |
Power rating - </=500 VA/60 W (safe area), </=16 VA/32 W (zone 2) |
Continuous current - </=2 A AC/DC (safe area, zone 2) |
Alarm function - line interruption at the input, short-circuit at input, no supply voltage, device error |
Nominal switching voltage - </=125 VAC/110 VDC (safe area), </=32 VAC/32 VDC (zone 2) |
Power rating - </=62.5 VA/32 W (safe area), </=16 VA/32 W (zone 2) |
Alarm output type - relay, 1 NC (voltage-free) |
Continuous current - </=0.5 A AC/0.3 A DC (safe zone), </=0.5 A AC/1 A DC (zone 2) |