Telemecanique XMLA035C2C11 XMLA Series Fixed Differential, Pressure Sensor sensing
Pressure Sensors
PDW~13604000
MFG #: XMLA035C2C11
Telemecanique Sensors
429.00000
/ ea
Telemecanique XMLA035C2C11, Fixed Differential, XMLA Series, Pressure Sensor Sensing Method, 3 A, Male connector Connection, 507.63 psi Pressure, 4.45 in H x 1.38 in W x 2.95 in D Size, IP65 Enclosure, -25 to 70 deg C Operating, Environmental Conditions: -40 to 158
- Brochure URL - 0b5fe79f8ef9559d0bb70d9e5752815d10f99bab.pdf(Brochure URL)
- Computer~Aided [CAD|BIM] Model URL(Computer~Aided [CAD|BIM] Model URL)
- Install Instructions 1 URL - 11003_L1ZDKBRYWTU4097A.pdf(Install Instructions 1 URL)
- Seller Home Page URL - us(Seller Home Page URL)
- Spec Sheet URL - 11003_9MBCEFUG6HSZ13D4.pdf(Spec Sheet URL)
- Applications
- Features
Detection of 1 single threshold;-;Control circuit |
With local display |
6 kV EN/IEC 60947-1 uimp rated impulse withstand voltage |
Corrosive fluid 32 to 320 deg F (0 to 160 deg C)) controlled fluid |
21.76 to 507.63 psi (1.5 to 35 bar) adjustable range of switching point on rising pressure |
Diaphragm pressure actuator |
18.13 psi (1.25 bar) +/- 0.25 bar) natural differential at low setting |
18.13 psi (1.25 bar) +/- 0.25 bar) natural differential at high setting |
652.67 psi (45 bar) maximum permissible pressure - per cycle |
300 V UL 508500 V EN/IEC 60947-1300 V CSA C22.2 No 14 ui rated insulation voltage |
25 mOhm IEC 255-7 category 325 mOhm NF C 93-050 method A maximum resistance across terminals |
25 mOhm IEC 255-7 category 325 mOhm NF C 93-050 method A maximum resistance across terminals |
10 A cartridge fuse gG (gl) short-circuit protection |
5000000 cycles mechanical durability |
External setting |
TC standard version protective treatment |
Any position operating position |
Class I IEC 1140Class I IEC 536Class I NF C 20-030 electrical shock protection class |