Telemecanique XMLA002A2C11 XMLA Series Fixed Differential, Pressure Sensor sensing
Pressure Sensors
PDW~12913671
MFG #: XMLA002A2C11
Telemecanique Sensors
238.00000
/ ea
Telemecanique XMLA002A2C11, Fixed Differential, XMLA Series, Pressure Sensor Sensing Method, 3 A, Male connector Connection, 36.26 psi Pressure, 6.22 in H x 1.38 in W x 35 in D Size, IP65 Enclosure, -25 to 70 deg C Operating, Environmental Conditions: -40 to 158
- Brochure URL - 11003_327LTIKVBZQF6MYS.pdf(Brochure URL)
- Computer~Aided [CAD|BIM] Model URL - files?p_enDocType=CAD&p_File_Name=MCADID0003744.pdf(Computer~Aided [CAD|BIM] Model URL)
- Spec Sheet URL - 11003_UG51RETVWPYQ4NJB.pdf(Spec Sheet URL)
- Seller Home Page URL - us(Seller Home Page URL)
- Install Instructions 1 URL - 11003_L1ZDKBRYWTU4097A.pdf(Install Instructions 1 URL)
- Applications
- Features
For detection of a single pressure threshold in air, fresh water and hydraulic oi |
With local display |
6 kV EN/IEC 60947-1 uimp rated impulse withstand voltage |
Air 32 to 158 deg F (0 to 70 deg C))Fresh water 32 to 158 deg F (0 to 70 deg C))Hydraulic oil 32 to 158 deg F (0 to 70 deg C)) controlled fluid |
2.18 to 36.26 psi (0.15 to 2.5 bar) adjustable range of switching point on rising pressure |
Diaphragm pressure actuator |
1.89 psi (0.13 bar) +/- 03 bar) natural differential at low setting |
1.89 psi (0.13 bar) +/- 03 bar) natural differential at high setting |
72.52 psi (5 bar) maximum permissible pressure - per cycle |
300 V UL 508500 V EN/IEC 60947-1300 V CSA C22.2 No 14 ui rated insulation voltage |
25 mOhm IEC 255-7 category 325 mOhm NF C 93-050 method A maximum resistance across terminals |
25 mOhm IEC 255-7 category 325 mOhm NF C 93-050 method A maximum resistance across terminals |
10 A cartridge fuse gG (gl) short-circuit protection |
8000000 cycles mechanical durability |
External setting |
TC standard version protective treatment |
Any position operating position |
Class I IEC 1140Class I IEC 536Class I NF C 20-030 electrical shock protection class |