Square D™ TeSys® LC1F330 3-Phase IEC Contactor With Coil, 600 VAC V Coil, 330 A, 3NO Contact, 3 Poles
NEMA & IEC Contactors
100066
MFG #: LC1F330
Square D™
1807.06000
/ ea
Square D™ TeSys® IEC Contactor, 3-Phase, Series: LC1F, 600 VAC Coil, 330 A Maximum Load Current, 160 kW Coil, 3 Pole, 50/60 Hz Frequency, 44/31 W Wattage, Non-Reversing Contact, 3NO Contact Configuration, 600 VAC, 330 A Inductive, 400 A Resistive Contact, Bolt-On/Lug Terminal, IP20 Enclosure, 10000000 cycles Operating Cycles, -5 to 55 deg C Operating, Panel Mounting, 8.39 in W x 8.62 in D x 8.11 in H Dimensions
- Brochure URL - 11003_KSGYFRZ9O1J6MP3N.pdf(Brochure URL)
- Computer~Aided [CAD|BIM] Model URL(Computer~Aided [CAD|BIM] Model URL)
- Install Instructions 1 URL - 11003_WPRQF1HY3JVAKSU6.pdf(Install Instructions 1 URL)
- Computer~Aided [CAD|BIM] Model URL - files?p_enDocType=CAD&p_File_Name=MCADPD0004419.pdf(Computer~Aided [CAD|BIM] Model URL)
- Seller Home Page URL - us(Seller Home Page URL)
- Service Manual URL - 11003_3B8D4APYGK25W16M.pdf(Service Manual URL)
- Tech Drawing URL - 11003_8RAN9SCQKF4V2GMT.dxf(Tech Drawing URL)
- Spec Sheet URL - 11003_5VE6OB2QU0LMYNXK.pdf(Spec Sheet URL)
- Tech Bulletin URL - 11003_8G547S3DJIOHPNLZ.pdf(Tech Bulletin URL)
- Video - https://www.youtube.com/embed/GW6XwNd-Fek(Video)
- Service Manual URL - 11003_4B8RSO5LX2YCKNQJ.pdf(Service Manual URL)
- Tech Drawing URL - files?p_enDocType=Technical+Drawing&p_File_Name=LC1F330S.dxf(Tech Drawing URL)
- Tech Bulletin URL - 11003_R8DPHVO6FAXJE9S2.pdf(Tech Bulletin URL)
- Spec Sheet URL - 11003_QB70AGP5T6UHZMKD.pdf(Spec Sheet URL)
- Applications
- Features
For motor control and resistive load applications |
8 kv-rated impulse withstand voltage |
III overvoltage category |
400 a at 104 deg f conventional-free air thermal current |
2640 a conforming to IEC 60947-4-1 rated breaking capacity |
400 a aM at 440 V/500 a gG at 440 V associated fuse rating |
0.28 mohm at 50 Hz to 400 a average impedance |
1000 V conforming to IEC 60947-4-1/1500 V conforming to VDE 0110 group c rated insulation voltage |
88.5 in-lb tightening torque power circuit |
100 to 170 ms closing, 40 to 65 ms opening operating time |
650 VA at 68 deg f 40 to 400 Hz inrush power |
650 VA at 68 deg f 40 to 400 Hz inrush power |
10 VA at 68 deg f 40 to 400 Hz hold-in power consumption |
8 W heat dissipation |
TH protective treatment |
-40 to 158 deg f permissible ambient air temperature around the device |
9842.52 ft without derating in temperature operating altitude |
Vibrations contactor closed 6 gn, 5 to 300 Hz/shocks contactor open 9 gn for 11 ms/vibrations contactor open 2 gn, 5 to 300 Hz/shocks contactor closed 15 gn for 11 ms mechanical robustness |
160 kW at 380 to 400 vac 50/60 Hz AC-3, 200 kW at 500 vac 50/60 Hz AC-3, 180 kW at 415 vac 50/60 Hz AC-3, 200 kW at 440 vac 50/60 Hz AC-3 motor power |
220 kW at 660 to 690 vac 50/60 Hz AC-3, 160 kW at 1000 vac 50/60 Hz AC-3, 100 kW at 220 to 230 vac 50/60 Hz AC-3, 59 kW at 400 vac 50/60 Hz AC-4 motor power |
44 W (AC-1), 31 W (AC-3) power dissipation per pole |