Square D™ PCSP060D5IP31, 60 A, 50 to 60 Hz, Floor Standing mount
General Purpose Line Filters
PDW~13601800
MFG #: PCSP060D5IP31
Square D™
0.00000
/ ea
- Brochure URL - 11003_SCPNMVBTRU0321WZ.pdf(Brochure URL)
- Computer~Aided [CAD|BIM] Model URL(Computer~Aided [CAD|BIM] Model URL)
- Seller Home Page URL - us(Seller Home Page URL)
- Service Manual URL - 11003_MPZOAJEC829W7FIQ.pdf(Service Manual URL)
- Spec Sheet URL - 11003_VOJRS7HI9DEMBWY8.pdf(Spec Sheet URL)
- Tech Drawing URL - 11003_H2V06NGD75QMLR9U.pdf(Tech Drawing URL)
- Tech Drawing URL - 11003_XT6OEL9AQ0SC32HI.pdf(Tech Drawing URL)
- User Manual URL - 11003_UH5PE68C3GFKVOQ0.pdf(User Manual URL)
- User Manual URL - files?p_enDocType=User guide&p_File_Name=NHA71460-02.pdf(User Manual URL)
- Applications
- Features
For harsh electrical conditions, for heavy industrial applications including miss |
A complete solution for harmonic filtering that meets every harmonic standard around the world |
Can be operated as a displacement power factor correction and load balancing device independent of or in conjunction with harmonic mitigation |
Relative humidity to 95 %, noncondensing |
Operating Altitude 1000 m (derate 1 %/100 m above), max 4800 m |
Display 144 mm QVGA TFT 64k-color touchscreen |
3P network type |
3 or 4-wires network configuration |
380 to 480 V AC network rated voltage |
50/60 Hz +/- 3 Hz auto sensing input frequency |
Not provided neutral correction |
Not provided neutral correction |
60 A rms output current rating |
Power factor correctionMains current balancingHarmonic cancellation operating modes |
Indoor installation location |
Circuit breaker protection type |
200 kA interrupt capacity |
Top or bottom location of connection |
IP31 enclosure degree of protection |
Operating 3C2 IEC 60721-3-3Operating 3S2 IEC 60721-3-3Storage 3C3 IEC 60721-3-3Storage 3S3 IEC 60721-3-3 environmental characteristic |
<= 3280.84 ft (1000 m) 1 % per 100 m operating altitude |