TESYS U SIMPLE MOTOR STARTER
INCLUDES 1N/O AND 1 N/C AUXILIARY CONTACT.
Suitability for isolation
10 kA 500 V, 4 kA 690 V, 50 kA 230 V, 50 kA 440 V rated service breaking capacity
130 mA at 24 VDC I maximum while closing with LUCA, LUCB, LUCC, LUCD, 140 mA at 24 VAC I maximum while closing with LUCA, LUCB, LUCC, LUCD, 150 mA at 24 VDC I maximum while closing with LUCM, 280 mA at 110 to 220 VDC I maximum while closing with LUCA, LUCB, LUCC, LUCD
35 ms opening with LUCA, LUCB, LUCC, LUCD, LUCM control circuit, 50 ms at >= 72 V closing with LUCA, LUCB, LUCC, LUCD control circuit, 60 ms at 48 V closing with LUCA, LUCB, LUCC, LUCD control circuit, 70 ms at 24 V closing with LUCA, LUCB, LUCC, LUCD control circuit, 75 ms closing with LUCM control circuit operating time
15000000 cycles mechanical durability, 60 cycles/min operating rate, 6 kV conforming to IEC 60947-6-2 rated impulse withstand voltage, 600 V conforming to CSA C22.2 No 14, 600 V conforming to UL 508, 690 V conforming to IEC 60947-1 3 rated insulation voltage
Control circuit: 7.08-10.62 lbf.in- with screwdriver 0.2 in flat, control circuit: 7.08-10.62 lbf.in - with screwdriver 0.2 in Philips no 1, power circuit: 16.81-22.12 lbf.in- with screwdriver 0.24 in flat, power circuit: 16.81-22.12 lbf.in - with screwdriver 0.24 in Philips no 2 tightening torque
2 W for control circuit with LUCA, LUCB, LUCC, LUCD, 1.7 W for control circuit with LUCM heat dissipation
IP20 front panel and wired terminals conforming to IEC 60947-1, IP20 other faces conforming to IEC 60947-1, IP40 front panel outside connection zone conforming to IEC 60947-1 IP degree of protection
TH conforming to IEC 60068 protective treatment
1 kV serial mode 24 to 240 VAC conforming to IEC 60947-6-2, 1 kV serial mode 48 to 220 VDC conforming to IEC 60947-6-2, 2 kV common mode 24 to 240 VAC conforming to IEC 60947-6-2, 2 kV common mode 48 to 220 VDC conforming to IEC 60947-6-2 non-dissipating shock wave, 10 V conforming to IEC 61000-4-6 immunity to radio electric fields
1.5 hp at 1 phase 115 VAC, 2 hp at 1 phase 230 VAC, 10 hp at 3 phase 575 VAC, 3 hp at 3 phase 230 VAC, 3 hp at 3 phase 200 VAC, 7.5 hp at 3 phase 460 VAC power rating
-13 to 140 deg F with LUCM/-13 to 158 deg F with LUCA, LUCB, LUCC, LUCD