Siemens 3RV2 Plant Protection Circuit Breaker, 690 VAC, 20 A, 65 kA Interrupt, 3 Poles, Thermal Trip
Motor Protection Circuit Breakers
1092490
MFG #: 3RV27425CD10
Siemens
719.77000
/ ea
Siemens Circuit Breaker, Plant Protection, Series: 3RV2, 690 VAC, 20 A, 7500 W at 400 VAC, 50 to 60 Hz, 65 kA Interrupt, S3 Frame, Thermal Trip, 260 A Trip, 3 Poles, Screw, IP20, Threaded/Snap-On Mount, -20 to 60 deg C, 170 mm H x 70 mm W x 176 mm D
- 3D Rendering URL - G_IC03_XX_19000V.pdf(3D Rendering URL)
- http://www.sea.siemens.com(Seller Home Page URL)
- Spec Sheet URL - 10991_PLMNE4OR09V2I15Y.pdf(Spec Sheet URL)
- Spec Sheet URL - DatasheetService?format=PDF&caller=EGH&mlfbs=3RV27425CD10&language=en(Spec Sheet URL)
- Spec Sheet URL - DatasheetService?format=PDF&caller=EGH&mlfbs=3RV2742-5CD10&language=en(Spec Sheet URL)
- Spec Sheet URL - DatasheetService?format=PDF&caller=PDPS&mlfbs=3RV2742-5CD10&language=en(Spec Sheet URL)
- User Manual URL - man(User Manual URL)
- Video - https://www.youtube.com/embed/5Oq25B99HBo(Video)
- Features
Minimization of energy losses through optimization of the bimetal trip units |
Reduction of inherent power loss |
Less heating of the control cabinet |
Smaller control cabinet air conditioners can be used |
3RV2 motor starter protectors/circuit breakers are suitable for operation in IT systems (IT networks) |
7500 W at 400 VAC |
100 kA at 240 VAC, 100 kA at 400 VAC |
20 A thermal overload release, 260 A instantaneous overcurrent release |
Without auxiliary switch |