Features: Wire Range: Line Side: (1) 3/0 - 14 AWG (70 SQ-MM - 2.5 SQ-MM); Load Side: (4) 2 - 14 AWG (25 SQ-MM - 2.5 SQ-MM); Electrical Ratings: 200 AMP Copper Wire, 155 AMP Aluminum Wire (Based On NEC Table 310-16, 75 DEG C Columns); UL Listed At 600 Volts AC/DC Per UL-1953; UL 508A Feeder Circuit Terminal Spacing For Up To 600 Volts; CSA Certified At 600V AC/DC Per CSA C22.2 No. 158. (Class-C, General Industrial); CE Rated Voltage (Ui): 1000 V AC/DC Per IEC 60947-7-1; Minimum Enclosure Size: 16 X 12 X 6; Factory And Field Wiring; Mechanical Ratings: Maximum Insulator Base Temperature: 125 DEG C (257 DEG F) UL RTI; Flammability Rating Of Insulator Base: UL 94 V-0; Touch Protection: IP-20 (IEC 60529); Use Outside These Ratings Needs To Be Judged In The End-Use Application; Materials: Connector: High Conductivity Aluminum, Tin Plated; Insulator Base: Glass Filled P |