Leviton® ODS10-IDE OCCUPANCY SENSOR
Occupancy Sensors
868648
MFG #: ODS10-IDE
Leviton®
58.33000
/ ea
- http://www.leviton.com(Seller Home Page URL)
- Install Instructions URL - Leviton_ODS0D_IAW_Installation_Sheet.pdf(Install Instructions URL)
- Spec Sheet URL - 10962_ID-SPE-v1-ODS10-IDE.pdf(Spec Sheet URL)
- Safety Data Sheet URL - MSDS.pdf(Safety Data Sheet URL)
- Spec Sheet 1 URL - Leviton_ODS0D_IAW_Data_Sheet_1.pdf(Spec Sheet 1 URL)
- Tech Bulletin URL - Leviton_ODC0P_W_Technical_Bulletin.pdf(Tech Bulletin URL)
- Video - https://www.youtube.com/embed/vkM-Ppc9l-s(Video)
- Applications
- Features
Commercial |
Passive Infrared |
Fits in standard wallbox and replaces 1-pole wall switch, gangable with other units |
Low profile design eliminates obtrusive "scanning-device" look |
Convenient pushbutton provides manual ON/OFF light switching at any time |
Two dual element PIR sensors used to widen detection range |
Segmented fresnel lens provides optimum sensitivity and performance designed with an extensive "minor motion" area where even slight body movements will be detected |
Vandal resistant PIR lens |
Horizontal field-of-view may be adjusted between 180 and 60 deg of arc by using integral blinders located on either side of the lens, no masking tape required |
Manual ON/auto OFF mode for installations where manual ON switching is required but auto OFF switching is still desired for CEC title T24 energy savings |
To comply with T24, red LED indicator light flashes when sensor detects motion to verify detection is active |
Time delay adjustment for delayed OFF time settings of 30 sec (for walking test), 10, 20 and 30 min, allows customized adjustments to maximize energy savings |
Light sensor adjustable ambient light override ranges from approximately 20 to 5000+ LUX to prevent lights from turning ON automatically during periods of ample natural light, increasing energy savings |
Light sensor enables the load hold OFF feature once level has been set |
Vacancy confirmation when the time out expires and the lights turns OFF, a 30 sec vacancy confirmation exists to turn the lights back ON |
False detection circuitry |
Presentation mode feature for slide or film presentations allows pushbuttons to turn lights OFF and keep them OFF while the room is occupied |
1-unit can be used for 120 to 277 VAC lighting |
Compatible with both electronic and magnetic ballasts |
Relay switches at the zero crossing point of the AC power curve to ensure maximum contact life and compatibility with electronic ballasts |
Exclusive Leviton® high inrush stability (HIS) circuitry, specifically designed to handle today's high inrush electronic ballast loads and offer unmatched durability and service |
No neutral design is optional for retrofit applications |