Killark® XAS-53 FIRE ALARM BREAK GLASS
Fire Alarm Control Stations
494698
MFG #: XAS-53
Killark
1815.89000
/ ea
- http://www.hubbell-killark.com/(Seller Home Page URL)
- Install Instructions 1 URL - 11161_RZP58JFNWHAX9DOK.pdf(Install Instructions 1 URL)
- Spec Sheet URL - 11161_ZRE6TLKQ8GUH91VJ.pdf(Spec Sheet URL)
- Warranty URL - 11161_ID-WAR-Warranty_Front_Pages_DNC_4-1-2011.pdf(Warranty URL)
- Warranty URL - Warranty_Front_Pages_DNC_4-1-2011.pdf(Warranty URL)
- Applications
- Features
Hazardous areas due to the presence of flammable gases or vapors, combustible dusts, or easily ignitable fibers or flyings. Installation at petroleum refineries, chemical and petrochemical plants, storage areas, and other processing facilities where hazardous substances are handled or stored. Areas where emergency control of fire alarm or signal circuits is required. |
Killark XCS Series Fire Alarm Station for Class 1 Division 1 & 2, Class 1 Zone 1 & 2 areas where Type 7 & 9 protection is required. |
Enclosure is made of copper-free aluminum alloy |
Conduit openings are 3/4 in NPT feed through |
Red, textured powder epoxy paint finish is standard on box and cover and provides high visibility for alarm station |
Breaking glass with hammer provided activates alarm |
Reset by replacing glass |
7200 VA make, 720 VA break, 10 A continuous at 600 VAC 2.5 A continuous at 600 VDC contact rating |