• Applications
  • Features
SEAL-X Series is used to prevent the igniting of external hazardous atmospheres by the enclosed arcing devices in such areas as: hazardous locations due to the presence of flammable gases or vapors, combustible dusts or easily ignitable fibers or flyings
Killark SEAL-X Series Factory Sealed Control Stations provide control solutions in hazardous location areas to supply; START/STOP Motor Functions, LED Pilot Light Indications and more. Utilized in Class 1 Division 1 & 2, Class 1 Zone 1 & 2 areas where Type 3, 7 & 9 protection ratings are required for indoor and outdoor use. UL Listed and CSA Certified.
Eliminates external sealing requirements
Lower installation cost
NEMA 3 weatherproof
Color coded wiring with more wiring space for easier field installation
Stainless steel captive screws for cover
Ground boss for grounding in the splice box
Device covers are cast copper-free aluminum alloy
Pushbutton and pilot light bodies are copper-free aluminum
Operating shaft in pushbuttons are stainless steel
60 A inrush at 120 VAC, 30 A inrush at 240 VAC, 15 A inrush at 480 VAC, 12 A inrush at 600 VAC, 6 A breaking at 120 VAC, 3 A breaking at 240 VAC, 1.5 A breaking at 480 VAC, 1.2 A breaking at 600 VAC, 10 A carrying at 120 VAC, 10 A carrying at 240 VAC, 10 A carrying at 480 VAC contact rating
0.025 A at 120 VAC pilot light, 0.55 A inrush at 125 VDC, 0.275 A inrush at 250 VDC, 0.55 A breaking at 125 VDC, 0.275 A breaking at 250 VDC, 2.5 A carrying at 125/250 VDC pushbutton