• Features
Warranty: 2 year
New installations for proper insulation
Digital display with analog arc
Protective rubber boot
Backlit display auto sensing
Low battery indication
Tests voltages at 50/100/250/500/1000 volt
Open circuit voltage - <1.3 x V0, accuracy of nominal voltage - 0% to +10%, short circuit current - <3.0 mA, nominal testing current - 1 mA at 1 V (1 mA at 500 kOhm)
32 to 104 deg F temperature rating
0 - 4/40/400/4000M Ohm insulation resistance, 0.01 - 20 Ohm continuity
Insulation resistance range - 0.001 - 0.1 MOhm, 0.101 - 3.999 MOhm, 4 - 39.99 MOhm, 40 - 399.9 MOhm, 400 - 1000MOhm at 250 V, 0.001 - 0.25 MOhm, 0.251 - 3.999 MOhm, 4 - 39.99 MOhm, 40 - 399.9 Mohm, 400 - 2000 MOhm at 500 V, 0.001 - 0.25 MOhm, 0.251 - 3.999 MOhm, 4.00 - 39.99 MOhm, 40.0 - 399.9 MOhm, 400 - 1000 MOhm, 1000 - 4000 MOhm at 1000 V