For preventing passage of gases, vapors or flames from one portion of conduit system to another; Required in Class I, Division 1 and 2 locations within 18 IN of enclosures containing apparatus that may cause arcs, sparks or high temperatures; Required in Class I, Division 1 and 2 locations where 2 IN or larger conduit enters enclosure, fitting housing terminals, splices or taps; Required in Class I, Division 1 and 2 locations at the boundary where conduit leaves classified location; Required in Class I, Division 1 and 2 locations where two or more enclosures are connected by 36 IN or less conduit, seal must be located within 18 IN of either enclosure; Required where cables (which exceed rate of gas or vapor transmission permitted for seals) are used in Class I, Division 2 locations; Explosionproof, dust-ignitionproof, raintight; Smooth, rounded integral bushing in each hub protects conductor insulation; Accurately tapped, tapered threads for tight, rigid joints and ground continuity; F |
Smooth, rounded integral bushing in each hub protects conductor insulation |
Accurately tapped, tapered hub threads for tight, rigid joints and ground continuity |
Removable nipple in male sealing fitting may be used interchangeably in top or bottom hub |
For sealing vertical or horizontal conduit |
Pouring spout rotates 90 deg |
Removable cover provides full access for damming 1/2 to 1 in sizes have threaded cover openings for damming |
1-1/4 in turning radius |
Triple coat of zinc electroplate, chromate and epoxy powder coated finish |
Prevent passage of gases, vapors or flames from one portion of conduit system to another |
Restrict any explosion to the sealed off enclosure |
Required in class I, Division 1 and 2 locations within 18 in of enclosures containing apparatus that may cause arcs, sparks or high temperatures |
Required in class I, Division 1 and 2 locations where 2 in or larger conduit enters enclosure, fitting housing terminals, splices or taps |
Required in class I, Division 1 and 2 locations at the boundary where conduit leaves classified location |
Required in class I, Division 1 and 2 locations where two or more enclosures are connected by 36 in or less conduit |
Seal must be located within 18 in of either enclosure |
Seal must be located within 18 in of either enclosure |
Required where cables (which exceed rate of gas or vapor transmission permitted for seals) are used in Class I, Division 2 locations |