Marathon® 1112 1100 Heavy Duty Deadfront Terminal Block, 600 VAC/VDC, 65 A, 6 to 18 AWG Size
Dead Front Terminal Blocks
497860
MFG #: 1112
Marathon®
105.29000
/ ea
- Amperage Rating: 65 A
- Catalog Number: 1112
- Country of Origin: USA
- Gross Weight Per Pack: 1 lb
- Material: Connector: Tin Plated Aluminum; Insulator Base: Phenolic; Terminal Set Screws: Tin Plated Brass; Marking Strip: White Vinyl; Screws: Zinc Plated Steel
- Mounting: 5.620 IN Mounting Hole Distance
- Size: 6 IN Length X 1.380 IN Width X 130 IN Height
- Standard: UL Recognized, UL 1059 Terminal Block Standard, File No. XCFR2.E62806, CSA Certified, CSA C22.2 No. 158, File No. LR19766, CE Compliant IEC 60947-7-1, RoHS Compliant
- Standards: UL XCFR2.E62806, CSA LR19766, CE Certified, IEC 60947-7-1, RoHS Compliant
- Type: Heavy Duty, Deadfront, 100 Series
- UNSPSC: 39121410
- UPC 11: 78433761112
- UPC 12: 78433761112
- Voltage Rating: 600 VAC//VDC
- Wire Size: 6 - 18 AWG Copper, - 12 AWG Aluminum
- Stock Status: NONSTOCK
- Brand: Marathon®
- Manufacturer: Marathon Special Products
- Features
Features: Wire Range: - 18 AWG Copper, - 12 AWG Aluminum; Electrical Ratings: 65 AMP (Based On NEC Table 310-16, 75 ° C Columns); 600 Volts AC/DC (UL 1059 Class C, Use Group - General Industrial); Short Circuit Current Rated For 10,000 AMP; Factory And Field Wiring; Mechanical Ratings: Maximum Insulator Base Temperature Rating: 150 ° C (302 ° F) UL RTI; Storage And Transportation Temperature Range: -35 ° C To 125 ° C (-31 ° F To 257 ° F); Flammability Rating Of Insulator Base: UL 94 V-0; Use Outside These Ratings Needs To Be Judged In The End-Use Application; Materials: Connector: Aluminum, Tin Plated; Insulator Base: Phenolic; Terminal Set Screws: Brass, Tin Plated; Marking Strip: Vinyl (White); Marking Strip Screws: Steel, Zinc Plated; Agency Approvals: UL Recognized, UL 1059 Terminal Block Standard, File No. XCFR2.E62806; CSA Certified, CSA C |
12 poles |
Aluminum, tin plated connector |
Steel, nickel plated terminal set screw |
10,000 A short circuit current rating |
Steel, zinc plated marking strip screws |
UL 94V-0 flammability rating of insulator base |
Use outside these ratings needs to be judged in the end-use application |
-35 deg C to 125 deg C storage and transportation temperature range |
9/16 in wire strip length |
4 - 14 AWG copper, 4 - 8 AWG aluminum wire range |