Square D™ 330T145HDIT Dry Ventilated Drive Isolation Transformer, 460 Delta VAC Primary, 460Y/265 VAC Secondary, 330 kVA Power Rating, 60 Hz, 3 Phase
Drive Isolation Transformers
877917
MFG #: 330T145HDIT
Square D™
60269.11000
/ ea
- Alternate Catalog Number: 330T145HDIT
- Application: SCR Controlled Heating or Furnaces, 3-ph Rectifier Input DC Power Supplies, 3-ph Switched Mode Power Supplies and General Purpose Applications
- ARRA Compliant: N
- Buy American Compliant: N
- Catalog Number: 330T145HDIT
- Country of Origin: MX
- Currency: USD
- Enclosure: NEMA 2,ALUMINIUM
- EU RoHS Indicator: Y
- Gross Weight Per Pack: 1580.2700 lb
- Gross Weight per Pack Metric: 716.80
- Gross Weight UOM Metric: kg
- Harmonization Tariff Schedule Code: 8504330040
- Height: 50.27 in
- Height [Metric]: 128.9050 cm
- Item Group: 16266
- KVA Rating: 330 KVA
- Length: 32.69 in
- Length [Metric]: 83.8200 cm
- Material Composition Declaration: https://checkaproduct.se.com/DistantRequestDispatcher.aspx?action=export&pid=455713&lang=en-us
- NEMA Frame Size: 25D
- Returnable: N
- Tap Size: 2 5 % 1+ 1-
- Temperature Rating: 220 A°C ?°F
- Type: DRIVE ISOLATION TRANSFORMER
- UNSPSC: 39121029
- UPC 11: 78590130064
- UPC 12: 785901300649
- Warranty Description: Contractual Warranty:18 months
- Width: 41.61 in
- Width [Metric]: 106.6800 cm
- Stock Status: NONSTOCK
- Brand: Square D™
- Manufacturer: Schneider Electric
- Primary Voltage: 460 V DELTA V
- Secondary Voltage: 460Y/265 V
Square D™ Drive Isolation Transformer, Dry Ventilated, 460 Delta VAC Primary, 460Y/265 VAC Secondary, 330 kVA, 60 Hz, 3, 2 Taps, Floor Mount, Class B 428 deg F, NEMA 2, 150 deg C, 49-1/2 in H x 41 in W x 32 in D
- Brochure URL - 07d18b421a9c934d97f9052c1fc2a60e283d7b49.pdf(Brochure URL)
- Computer~Aided [CAD|BIM] Model URL - files?p_enDocType=CAD&p_File_Name=3688.dwg(Computer~Aided [CAD|BIM] Model URL)
- Computer~Aided [CAD|BIM] Model URL - files?p_enDocType=CAD&p_File_Name=3688.dxf(Computer~Aided [CAD|BIM] Model URL)
- Seller Home Page URL - us(Seller Home Page URL)
- Spec Sheet URL(Spec Sheet URL)
- Spec Sheet URL - 11003_5GMC0ERNOF7T8HZW.pdf(Spec Sheet URL)
- Tech Bulletin URL - 11003_6CEXJNYUDB0PGMQL.pdf(Tech Bulletin URL)
- Tech Bulletin URL - 11003_ZDGAB0M1QI7N95UC.pdf(Tech Bulletin URL)
- Tech Drawing URL - 11003_78OG4XRPFMCS0J2H.zip(Tech Drawing URL)
- Tech Drawing URL - 11003_K2TZ6FRXOI31AN9L.zip(Tech Drawing URL)
- User Manual URL - 11003_FVNW427MP6XS9UZ0.pdf(User Manual URL)
- User Manual URL - 11003_SP9W5RE32CJF1KH8.pdf(User Manual URL)
- Applications
- Features
SCR Controlled Heating or Furnaces, 3-ph Rectifier Input DC Power Supplies, 3-ph Switched Mode Power Supplies and General Purpose Applications |
DRIVE ISOLATION TRANSFORMER,ALUMINIUM |
Designed for the requirements of both adjustable frequency and DC motor drive power isolation, 6-pulse drive applications |
Meets 4% minimum reactance for 150 deg C temperature rise designs |
Conforms to IEEE-597 class B overload, which requires 150% of load for one minute per hour |
Designed for the thermal and mechanical stress of highly cyclic process control applications |
Drive isolation transformers provide reactive control of current harmonics for both AC and DC motor drives, either static bridge or SCR switch input type |
Aluminum windings |
(2) +/-1 at 5% taps |