Square D™ 220T145HDIT Dry Ventilated Drive Isolation Transformer, 460 Delta VAC Primary, 460Y/265 VAC Secondary, 220 kVA Power Rating, 60 Hz, 3 Phase

Drive Isolation Transformers
877916 MFG #: 220T145HDIT
Square D™
42859.80000 / ea
  • Alternate Catalog Number: 220T145HDIT
  • Application: SCR Controlled Heating or Furnaces, 3-Phase Rectifier Input DC Power Supplies, 3-Phase Switched Mode Power Supplies and General Purpose Applications
  • ARRA Compliant: N
  • Buy American Compliant: N
  • Catalog Number: 220T145HDIT
  • Country of Origin: UKN
  • Currency: USD
  • Enclosure: NEMA 2,ALUMINIUM
  • EU RoHS Indicator: Y
  • Gross Weight Per Pack: 0.1400 lb
  • Gross Weight per Pack Metric: 647.28
  • Gross Weight UOM Metric: kg
  • Harmonization Tariff Schedule Code: 8504330040
  • Height: 53.08 in
  • Height [Metric]: 136.1000 cm
  • Item Group: 16266
  • KVA Rating: 220 KVA
  • Length: 41.50 in
  • Length [Metric]: 106.4000 cm
  • Material Composition Declaration: https://checkaproduct.se.com/DistantRequestDispatcher.aspx?action=export&pid=455511&lang=en-us
  • NEMA Frame Size: 25D
  • Returnable: N
  • Tap Size: 2 5 % 1+ 1-
  • Temperature Rating: 220 A°C ?°F
  • Type: DRIVE ISOLATION TRANSFORMER
  • UNSPSC: 39121029
  • UPC 11: 78590183787
  • UPC 12: 785901837879
  • Warranty Description: Contractual Warranty:18 months
  • Width: 33.27 in
  • Width [Metric]: 85.3000 cm
  • Stock Status: NONSTOCK
  • Brand: Square D™
  • Manufacturer: Schneider Electric
  • Primary Voltage: 460 V DELTA V
  • Secondary Voltage: 460Y/265 V
Square D™ Drive Isolation Transformer, Dry Ventilated, 460 Delta VAC Primary, 460Y/265 VAC Secondary, 220 kVA, 60 Hz, 3, 2 Taps, Floor Mount, Class B 428 deg F, NEMA 2, 220 deg C, 49-1/2 in H x 41 in W x 32 in D
QTY
  • Applications
  • Features
SCR Controlled Heating or Furnaces, 3-Phase Rectifier Input DC Power Supplies, 3-Phase Switched Mode Power Supplies and General Purpose Applications
DRIVE ISOLATION TRANSFORMER,ALUMINIUM
Designed for the requirements of both adjustable frequency and DC motor drive power isolation, 6-pulse drive applications
Meets 4% minimum reactance for 150 deg C temperature rise designs
Conforms to IEEE-597 class B overload, which requires 150% of load for 1 min/hr
Designed for the thermal and mechanical stress of highly cyclic process control applications
Drive isolation transformers provide reactive control of current harmonics for both AC and DC motor drives, either static bridge or SCR switch input type
Aluminum winding
(2) +/-1 at 5% taps