Square D™ 11T144HDIT Dry Ventilated Drive Isolation Transformer, 460 Delta VAC Primary, 230Y/132 VAC Secondary, 11 kVA Power Rating, 60 Hz, 3 Phase

Drive Isolation Transformers
326887 MFG #: 11T144HDIT
Square D™
8050.25000 / ea
  • Alternate Catalog Number: 11T144HDIT
  • Application: SCR Controlled Heating or Furnaces, 3-ph Rectifier Input DC Power Supplies, 3-ph Switched Mode Power Supplies and General Purpose Applications
  • ARRA Compliant: N
  • Buy American Compliant: N
  • Catalog Number: 11T144HDIT
  • Country of Origin: US
  • Currency: USD
  • Dimensions: 27 in H x 20 in W x 16 in D
  • Enclosure: Aluminium
  • Enclosure Type: NEMA 2
  • EU RoHS Indicator: Y
  • Gross Weight Per Pack: 0.0200 lb
  • Gross Weight per Pack Metric: 88.45
  • Gross Weight UOM Metric: kg
  • Harmonization Tariff Schedule Code: 8504320000
  • Insulation: Class B 428 deg F
  • Item Group: 16266
  • KVA Rating: 11
  • Material Composition Declaration: https://checkaproduct.se.com/DistantRequestDispatcher.aspx?action=export&pid=455271&lang=en-us
  • Mounting Type: Floor
  • Number Of Taps: 2
  • Returnable: N
  • Temperature Rating: 150 ?°F
  • Type: Dry Ventilated
  • UNSPSC: 39121029
  • UPC 11: 78590178490
  • UPC 12: 785901784906
  • Warranty Description: Contractual Warranty:18 months
  • Stock Status: NONSTOCK
  • Brand: Square D™
  • Manufacturer: Schneider Electric
  • Frequency Rating: 60
  • Phase: 3
  • Power Rating: 11
  • Primary Voltage: 460 Delta VAC V
  • Secondary Voltage: 230Y/132 VAC
Square D™ Drive Isolation Transformer, Dry Ventilated, 460 Delta VAC Primary, 230Y/132 VAC Secondary, 11 kVA, 60 Hz, 3, 2 Taps, Floor Mount, Class B 428 deg F, NEMA 2, 150 deg C, 27 in H x 20 in W x 16 in D
QTY
  • Applications
  • Features
SCR Controlled Heating or Furnaces, 3-ph Rectifier Input DC Power Supplies, 3-ph Switched Mode Power Supplies and General Purpose Applications
Designed for the requirements of both adjustable frequency and DC motor drive power isolation, 6-pulse drive applications
Meets 4% minimum reactance for 150 deg C temperature rise designs
Conforms to IEEE-597 class B overload, which requires 150% of load for one minute per hour
Designed for the thermal and mechanical stress of highly cyclic process control applications
Drive isolation transformers provide reactive control of current harmonics for both AC and DC motor drives, either static bridge or SCR switch input type
Aluminum winding
(2) +/-1 at 5% taps