Schneider Electric 93T145HDIT TRANSFORMER DRY 3PH

Drive Isolation Transformers
413474 MFG #: 93T145HDIT
Square D™
22858.25000 / ea
  • Alternate Catalog Number: 93T145HDIT
  • ARRA Compliant: N
  • Buy American Compliant: N
  • Catalog Number: 93T145HDIT
  • Country of Origin: MX
  • Currency: USD
  • Dimensions: 43-3/4 in H x 32 in W x 27 in D
  • Enclosure: Aluminium
  • Enclosure Type: NEMA 2
  • EU RoHS Indicator: Y
  • Gross Weight Per Pack: 880.1500 lb
  • Gross Weight per Pack Metric: 399.23
  • Gross Weight UOM Metric: kg
  • Harmonization Tariff Schedule Code: 8504330040
  • Height: 45.32 in
  • Height [Metric]: 116.2050 cm
  • Insulation: Class B 428 deg F
  • Insulation Class: 150
  • Item Group: 16266
  • KVA Rating: 93
  • Length: 26.75 in
  • Length [Metric]: 68.5800 cm
  • Material Composition Declaration: https://checkaproduct.se.com/DistantRequestDispatcher.aspx?action=export&pid=456313&lang=en-us
  • Mounting Type: Floor
  • NEMA Frame Size: 22D
  • Number Of Taps: 2
  • Returnable: Y
  • Tap Size: 2 5 % 1+ 1-
  • Temperature Rating: 150 °C
  • Type: Dry Ventilated
  • UNSPSC: 39121029
  • UPC 11: 78590178607
  • UPC 12: 785901786078
  • Warranty Description: Contractual Warranty:18 months
  • Width: 31.70 in
  • Width [Metric]: 81.2800 cm
  • Stock Status: NONSTOCK
  • Brand: Square D™
  • Manufacturer: Schneider Electric
  • Frequency Rating: 60 Hz
  • Phase: 3
  • Power Rating: 93 kVA
  • Primary Voltage: 460 Delta VAC V
  • Secondary Voltage: 460Y/265 VAC
Schneider Electric 93T145HDIT TRANSFORMER DRY 3PH 93KVA 460V-460Y/265V
QTY
  • Features
DRIVE ISOLATION TRANSFORMER,ALUMINIUM
Designed for the requirements of both adjustable frequency and DC motor drive power isolation, 6-pulse drive applications
Meets 4% minimum reactance for 150 deg C temperature rise designs
Conforms to IEEE-597 class B overload, which requires 150% of load for one minute per hour
Designed for the thermal and mechanical stress of highly cyclic process control applications
Drive isolation transformers provide reactive control of current harmonics for both AC and DC motor drives, either static bridge or SCR switch input type
Aluminum windings
(2) +/-1 at 5% taps