HPS Drive Isolation DM275JJ DRIVE 3PH 275KVA 460-4
Drive Isolation Transformers
544317
MFG #: DM275JJ
HPS (Hammond Power Solutions)
10493.47000
/ ea
- Application: Variable Speed Drives.
- ARRA Compliant: C
- Buy American Compliant: C
- Catalog Number: DM275JJ
- Connection Type: Lug/Pad
- Cooling: Convection cooled
- Country of Origin: MUL
- Currency: USD
- Dimensions: 34 in L x 39-1/2 in W x 51-1/2 in H
- Enclosure: NJ1-N3R - Indoor or Outdoor
- Enclosure Type: NJ1-N3R Indoor/Outdoor
- EU RoHS Indicator: Y
- Gross Weight Per Pack: 1450.0000 lb
- Gross Weight per Pack Metric: 657.72
- Gross Weight UOM Metric: kg
- Harmonization Tariff Schedule Code: 8504330040
- Height: 51.50 in
- Height [Metric]: 130.8100 cm
- Insulation: 220
- KVA Rating: 275
- Length: 39.50 in
- Length [Metric]: 100.3300 cm
- Mounting: Floor Mount
- Mounting Type: Floor
- Number Of Phases: 3
- Standard: CSA, UL
- Standards: UL ListedCSA CertifiedRoHS Compliant
- Sub Brand: Standard Drive Isolation Transformer
- Temperature Rating: Typical 30 Average/ 40 Maximum °C
- Type: Transformers > Drive Isolation
- UNSPSC: 39121001
- UPC 11: 80342300425
- UPC 12: 803423004255
- Width: 34.00 in
- Width [Metric]: 86.3600 cm
- Stock Status: NONSTOCK
- Brand: HPS (Hammond Power Solutions)
- Manufacturer: Hammond Power Solutions
- Frequency Rating: 60 Hz
- Phase: 3 pH
- Power Rating: 275 kVA
- Primary Voltage: 460 V
- Secondary Voltage: 460Y V
HPS Drive Isolation Transformers are designed to meet the rugged demands of both AC and DC variable speed drives and also to provide the required voltage change. The separate primary and secondary windings provide electrical isolation between the incoming line and the SCR load. The windings are designed to withstand overcurrent of 150% of the rated load for 60 seconds or 200% of the rated load for 30 seconds. A duty cycle of one start for every two hours is permitted.
- Brochure URL - 11516_LP0IRMVJW59XOUA7.pdf(Brochure URL)
- Brochure URL - HPS-Tribune-Non-Efficient-Brochure.pdf(Brochure URL)
- Catalog 1 URL - HPS_DE027KD_Catalog_1.pdf(Catalog 1 URL)
- Catalog URL - IDW_DOCUMENT_7a78e1cd0bfb693ae735b09b09ee701c9ecf0a451c6dd3622abdc24f4023b347.pdf(Catalog URL)
- http://www.hammondpowersolutions.com(Seller Home Page URL)
- Install Instructions URL - HPS_DE027KD_Installation_Instructions.pdf(Install Instructions URL)
- Safety Data Sheet URL - HPS_MSDS.pdf(Safety Data Sheet URL)
- Spec Sheet URL - 11516_658J31FRXVUM2YE9.pdf(Spec Sheet URL)
- Spec Sheet URL - HPS-1%202kV-Class-Drive-Isolation-Transformer-Typical-Spec.pdf(Spec Sheet URL)
- Tech Bulletin URL - WebConfig.aspx?pn=DM275JJ(Tech Bulletin URL)
- Warranty URL - warranty-and-terms(Warranty URL)
- Applications
- Features
Variable Speed Drives. |
Designed to withstand overcurrent of 150% of the rated load for 60 seconds or 200% of the rated load for 30 seconds. Comes standard in an indoor/outdoor enclosure with a coil mounted thermal warning switch. |
Designed to withstand overcurrent of 150% of the rated load for 60 seconds or 200% of the rated load for 30 seconds |
Comes standard in an indoor/outdoor enclosure with a coil mounted thermal warning switch |
The separate primary and secondary windings provide electrical isolation between the incoming line and the SCR load |
Neutral terminal for field connection (on applicable units) |
Aluminum wound |
High grade non-aging, fully processed silicon steel laminations or better coil |
ST-20 compliant taps |
ANSI 61 UL 50 gray enclosure finish |
40 deg C maximum |