Acme Electric® T111685 Transformer 1PH 2KVA 120X240-12/24
Buck Boost Transformers
4223
MFG #: T111685
Acme Electric
396.06000
/ ea
- Application: For Low Voltage Lighting Or Control Circuitry
- ARRA Compliant: C
- Boost Voltage: 20.1 KVA/83.3 AMP: 220 V Line And 242 V Load
- Buy American Compliant: C
- Catalog Number: T111685
- Connection: Wire Lead Screw Terminal
- Country of Origin: MX
- Currency: USD
- Enclosure: NEMA 3R Steel
- Gross Weight Per Pack: 38.0000 lb
- Gross Weight per Pack Metric: 15.88
- Gross Weight UOM Metric: kg
- Harmonization Tariff Schedule Code: 8504320000
- Height: 13.00 in
- Height [Metric]: 33.0200 cm
- Insulation Class: 180 DEG C Class H
- Length: 5.13 in
- Length [Metric]: 13.0302 cm
- Maximum Output Current: 83.2/166 A
- Mounting: Wall
- Number Of Phases: 1
- Returnable: Y
- Standard: UL 506, UL File Number E79947V1, UL Control Number 50B8, UL Insulation Number X3221, CSA Certified, OSHA Compliant, ANSI, IEEE
- Temperature Rating: 115 °C
- Type: Buck-Boost Transformer
- UNSPSC: 39121025
- UPC 11: 04750308693
- UPC 12: 047503086933
- Width: 5.50 in
- Width [Metric]: 13.9700 cm
- Stock Status: NORMALLY STOCKED
- Brand: Acme Electric
- Manufacturer: Acme Electric
- Frequency Rating: 60 Hz
- Primary Voltage: 120/240
- Secondary Voltage: 12/24
Acme Electric T-1-11685 Transformer, Encapsulated Core And Coil Buck-Boost, 120/240 V, 12/24 V, 40.8 KVA/175 AMP: 252 V Line And 240 V Load Buck Voltage, 20.1 KVA/83.3 AMP: 220 V Line And 242 V Load Boost Voltage, 60 HZ, 1 PH, 166 AMP At 12 V, 83.2 AMP At 24 V, 115 DEG C Rise, Wire Lead Screw Terminal Connection, 180 DEG C Class H Insulation, Wall Mounting, NEMA 3R, 5-1/2 IN Length, 5.13 IN Width, 13 IN Height, 2 KVA, Steel, Configuration: Primary: Two Winding, Secondary: Two Winding, UL 506, UL File Number E79947V1, UL Control Number 50B8, UL Insulation Number X3221, CSA Certified, OSHA Compliant, ANSI, IEEE, For Low Voltage Lighting Or Control Circuitry
- Install Instructions 1 URL - 11112_GMEQCKR8X4L35ATS.pdf(Install Instructions 1 URL)
- Install Instructions 1 URL - 11112_HP5W1VA2YL0ZOUM3.pdf(Install Instructions 1 URL)
- Safety Data Sheet URL - HCC_SDS.pdf(Safety Data Sheet URL)
- Seller Home Page URL - en(Seller Home Page URL)
- Spec Sheet URL - 11112_OQVC4NXRB3P07G9M.pdf(Spec Sheet URL)
- Tech Drawing URL - Acme_BB2_TECHNICAL_DRAWINGS.dwg(Tech Drawing URL)
- Applications
- Features
For Low Voltage Lighting Or Control Circuitry |
Encapsulated core and coil; Buck-boost transformers are small single phase transformers designed to reduce (buck) or raise (boost) line voltage from 5 - 20 PCT; The most common example is boosting 208 - 230 V, usually to operate a 230 V motor such as an air-conditioner compressor, from a 208 V supply line; Buck-boost transformers are an economical way to correct a potentially very serious problem; Anytime a line voltage change in the 5 - 20 PCT range is required, a buck-boost transformer should be considered as your first line of defense; 10-year limited warranty |