Schneider Electric LUCB32ES TESYS Series, Earth Fault Protection/Manual Reset/Overload Protection/Phase Failure Protection/Phase Imbalance Protection/Short Circuit Protection function

Motor Control Modules
PDW~11740954 MFG #: LUCB32ES
Square D™
0.00000 / ea
  • Alternate Catalog Number: LUCB32ES
  • Application: For overload simulation, For diagnostics, it provides a thermal overload alarm to be managed with an additional function module, For m a TeSys U starter controller, for 3-phase motor applications up to 15kW, For the control of the starter
  • ARRA Compliant: N
  • Buy American Compliant: N
  • Catalog Number: LUCB32ES
  • Country of Origin: FR
  • Currency: USD
  • EU RoHS Indicator: Y
  • Gross Volume Per Pack: 61.02
  • Gross Volume per Pack Metric: 1000.00
  • Gross Volume UOM: CI
  • Gross Volume UOM Metric: cm3
  • Gross Weight Per Pack: 1.2500 lb
  • Gross Weight per Pack Metric: 125.00
  • Gross Weight UOM Metric: g
  • Harmonization Tariff Schedule Code: 8537109170
  • Height: 5.5000 in
  • Height [Metric]: 5.5000 cm
  • Item Group: 22397
  • Length: 8.6000 in
  • Length [Metric]: 8.6000 cm
  • Material Composition Declaration: https://checkaproduct.se.com/DistantRequestDispatcher.aspx?action=export&pid=640726&lang=en-us
  • Returnable: N
  • Substitute Product Catalog Number: LUFC00
  • UNSPSC: 43201542
  • Warranty Description: Contractual Warranty:18 months
  • Width: 10.2000 in
  • Width [Metric]: 10.2000 cm
  • Brand: Square D™
  • Manufacturer: Schneider Electric
QTY
  • Applications
  • Features
For overload simulation, For diagnostics, it provides a thermal overload alarm to be managed with an additional function module, For m a TeSys U starter controller, for 3-phase motor applications up to 15kW, For the control of the starter
TeSys U provides motor control for a wide range of applications, from a basic motor starter with solid state thermal overload protection to a sophisticated motor controller which communicates on networks and includes programmable motor protection
Using a plug-in modular design, TeSys U allows for maximum flexibility in motor control
The compact, 45 mm wide power base mounts on either a panel or a 35 mm DIN rail
The power base provides the main contacts (power poles) for the combination starter
12 A, 32 A and NEMA Size 1 in three available versions
The control unit provides the control and thermal overload functions for the power base
Interchangeable, wide-range control units provide motor protection from 0.15 to 32 amps
Standard provides Class 10 trip only with no communication capabilities
Advanced provides a choice of Class 10 or Class 20 trip and allows for network communications
Function modules offer customization for specific application requirements
Function modules offer customization for specific application requirements
Communication modules enable integration into existing automation architecture via a variety of protocols
3-phase motor self-cooled load type
8 to 32 A rated motor current adjustment range
Class 10 40 to 60 Hz -13 to 158 deg F (-25 to 70 deg C) IEC 60947-6-2Class 10 40 to 60 Hz -13 to 158 deg F (-25 to 70 deg C) UL 508 thermal overload class
14.2 x Ir +/- 20 % tripping threshold
With phase failure sensitivity
35 ms opening with LUB32 control circuit35 ms opening with LUB38 control circuit60 ms closing with LUB32 control circuit60 ms closing with LUB38 control circuit operating time
Manual reset reset
690 V IEC 60947-6-2600 V UL 60947-4-1600 V CSA C22.2 No 60947-4-1 ui rated insulation voltage