Schneider Electric LX1FK110 TeSys™ F Contactor Coil, 110/120 VAC, 40 to 400 Hz, For Use With LC1 Series Contactor

Motor Control Coils
408781 MFG #: LX1FK110
Schneider Electric
547.34000 / ea
  • Alternate Catalog Number: LX1FK110
  • Application: TeSys F LC1F contactor;LC1F500
  • ARRA Compliant: N
  • Buy American Compliant: N
  • Catalog Number: LX1FK110
  • Coil Power Rating: 18-18 VA 40...400 HZ 0.3 20 A°C)
  • Coil Voltage: 110/120@40/400Hz VAC
  • Country of Origin: CZ
  • Currency: USD
  • EU RoHS Indicator: Y
  • Gross Volume Per Pack: 178.08
  • Gross Volume per Pack Metric: 2918.20
  • Gross Volume UOM: CI
  • Gross Volume UOM Metric: cm3
  • Gross Weight Per Pack: 2.6900 lb
  • Gross Weight per Pack Metric: 1.26
  • Gross Weight UOM Metric: kg
  • Harmonization Tariff Schedule Code: 8504508000
  • Height: 9.6000 in
  • Height [Metric]: 9.6000 cm
  • Item Group: 22341
  • Length: 22.6000 in
  • Length [Metric]: 22.6000 cm
  • Material Composition Declaration: https://checkaproduct.se.com/DistantRequestDispatcher.aspx?action=export&pid=641408&lang=en-us
  • Operating Temperature: -5-55 A°C
  • Returnable: N
  • Series: LX1
  • Standards: ARRA, Buy American Act, RoHS Compliant
  • Sub Brand: TESYS
  • Type: CONTACTOR COIL
  • UNSPSC: 39121529
  • UPC 11: 78590108220
  • UPC 12: 785901082200
  • Warranty Description: Contractual Warranty:18 months
  • Width: 11.5000 in
  • Width [Metric]: 11.5000 cm
  • Stock Status: NONSTOCK
  • Brand: Schneider Electric
  • Manufacturer: Schneider Electric
  • Frequency Rating: 40 to 400 Hz
  • Suitable For Use With: LC1F500 Contactor
  • Voltage Rating: 110 to 120 VAC
QTY
  • Applications
  • Features
TeSys F LC1F contactor;LC1F500
WITHOUT BUILT-IN SUPPRESSOR MODULE
9.55 Ohm inrush at 20 deg C, 260 Ohm holding at 20 deg C average resistance
1.25 H inductance of closed circuit
100 to 170 ms closing, 40 to 65 ms opening operating time
10000000 cycles mechanical durability
2400 cycles/hr at <=131 deg F operating time
Without built-in suppressor module coil technology
0.3 to 0.5 Uc at 55 deg C drop-out 40 to 400 Hz, 0.85 to 1.1 Uc at 55 deg C operational 40 to 400 Hz control circuit voltage limits
1100 VA at 20 deg C (cos f 0.9) 40 to 400 Hz inrush power
18 VA at 20 deg C (cos f 0.3) 40 to 400 Hz hold-in power consumption
18 W at 40 to 400 Hz heat dissipation
>-5 to 55 deg C ambient air temperature for operation
AC control circuit