Bussmann® NON-200 Non-Indicating Non-Rejection Non-Renewable Fast Acting Fuse, 250 VAC/125 VDC, 200 A, 10 kA at 250 VAC

One-Time Fuses
112345 MFG #: NON-200
Bussmann
166.34000 / ea
  • Alternate Catalog Number: NON-200
  • Application: Ind Facilities & Factories - Facility: Safety and Security Systems
  • ARRA Compliant: C
  • Body Size: 1.56 in Dia x 7.13 in L
  • Buy American Compliant: C
  • Catalog Number: NON-200
  • Connection: Blade end x blade end
  • Country of Origin: MX
  • Currency: USD
  • Element: Single
  • EU RoHS Indicator: C
  • Gross Weight Per Pack: 0.8000 lb
  • Gross Weight per Pack Metric: 0.34
  • Gross Weight UOM Metric: kg
  • Harmonization Tariff Schedule Code: 8536100040
  • Height: 1.56 in
  • Height [Metric]: 3.9624 cm
  • Indicating|Non~Indicating: Non-Indicating
  • Length: 7.13 in
  • Length [Metric]: 18.1102 cm
  • Material: Melamine
  • Mounting Type: Holder
  • Rejection|Non~Rejection: Non-Rejection
  • Series: NON
  • Size: 1.56 In Diameter X 7.13 In Length
  • Standard: CE Marked
  • Sub Brand: Bussmann Series
  • Terminal Type: Blade
  • Type: Fuse
  • UNSPSC: 39121605
  • UPC 11: 05171210172
  • UPC 12: 051712101721
  • Width: 1.56 in
  • Width [Metric]: 3.9624 cm
  • Stock Status: NONSTOCK
  • Brand: Bussmann
  • Manufacturer: Eaton
  • Amperage Rating: 200 A
  • Body Type: Cartridge
  • Class: H
  • Interrupt Rating: 10 kAIC at 250 Vac kA
  • Voltage Rating: 250 V
QTY
  • Applications
  • Features
Ind Facilities & Factories - Facility: Safety and Security Systems
Non current limiting
Protect lighting, heating and other circuits not subject to temporary surges and where available short circuit currents are relatively low
Non one time fuses do not have any appreciable degree of time delay and thus should not be specified in circuits where large transients or motor overloads occur
For general purpose circuits, size at amp rating of circuit and motor circuits, size at 300% to 400%
For motor circuits, size at 300% to 400% according to the NEC® motor ampacity tables 430.247 to 430.250, per 430.6(A)(1)
For motor circuits, size at 300% to 400% according to the NEC® motor ampacity tables 430.247 to 430.250, per 430.6(A)(1)
10 kA VAC RMS symmetrical interrupt rating