Edison TCF60 CUBEFuse TCF Time Delay Fuse, 60 A, 600 VAC/300 VDC, 300/100 kA, Class CF, Square Body

Cube Shaped Fuses
45947 MFG #: TCF60
Bussmann
168.90000 / ea
  • Alternate Catalog Number: TCF60
  • ARRA Compliant: C
  • Body Size: 2.13 in L x 1 in W x 1.13 in H
  • Buy American Compliant: C
  • Catalog Number: TCF60
  • Connection: Blade end
  • Country of Origin: MUL
  • Currency: USD
  • Element: Dual
  • EU RoHS Indicator: C
  • Gross Weight Per Pack: 0.1850 lb
  • Gross Weight per Pack Metric: 0.95
  • Gross Weight UOM Metric: kg
  • Harmonization Tariff Schedule Code: 8536100040
  • Height: 2.17 in
  • Height [Metric]: 5.5118 cm
  • Length: 4.33 in
  • Length [Metric]: 10.9982 cm
  • Material: Glass filled PES
  • Mounting: 35 mm Din Rail, chassis
  • Mounting Type: DIN Rail
  • Response Time: 10 S at 500%
  • Series: TCF
  • Size: 2.13 In Length X 1.00 In Height
  • Standard: UL Listed ,CSA Certified,CE Marked,RoHS Compliant
  • Standards: ARRA CompliantBuy American Act CompliantRoHS CompliantUL Guide No. JFHR File No. E56412CSA C22.2 No. 248.12 Class 1422-02 File No. 53787CE Certified
  • Sub Brand: Bussmann Series
  • Terminal Type: Radial Blade Plug-In
  • Type: Fuse
  • UNSPSC: 39121606
  • UPC 11: 05171261508
  • UPC 12: 051712615082
  • Width: 6.10 in
  • Width [Metric]: 15.4940 cm
  • Stock Status: NORMALLY STOCKED
  • Brand: Bussmann
  • Manufacturer: Eaton
  • Amperage Rating: 60 A
  • Class: Class CF
  • Interrupt Rating: 300 kAIC at 600 Vac100 kAIC at 300 Vdc
  • Voltage Rating: 600//300 VAC//VDC
QTY
  • Applications
  • Features
Ind Facilities & Factories - Facility: Safety and Security SystemsDatacenters - Facilities: Power DistributionCommercial / Institutional Buildings / Structures - Critical PowerInd Facilities & Factories - Facility: Power Distribution and ControlStationary Machinery and Equipment Outside Factory - HVAC
Finger safe
The world's first finger safe power fuse system
Smallest footprint of any class fuse including class J, CC, T and RK
Meets class CF and class J time delay electrical performance requirements
The indicating version features easyID™ open fuse technology for faster troubleshooting and reduced downtime
Faster response to damaging faults to help reduce destructive thermal and magnetic forces
True dual element fuse construction with a minimum of 10 s time delay at 500% of rating
Long time delay minimizes nuisance circuit openings due to temporary overloads and transient surges
High interrupting rating to safely interrupt faults up to 300 kA
No venting of arc or molten metal and gases during opening
Robust cycling and inrush current withstand
Low let-through currents under fault conditions
Provides type 2 "no damage" protection for IEC motors starters when properly sized
Easy selective coordination with any other Cooper Bussmann Low-Peak™
Class CC, L, J and RK1 fuse with simple 2:1 amp ration between upstream and downstream fuses
35 mm DIN rail mount
300 kA RMS symmetrical UL, 200 kA RMS symmetrical CSA, 100 kA DC UL/CSA rated interrupt rating
10 s at 500% response time