Schneider Electric ATV212HU22N4 SPEEDDRIVE 380-480

AC Drives
612443 MFG #: ATV212HU22N4
Schneider Electric
945.54000 / ea
  • Alternate Catalog Number: ATV212HU22N4
  • Application: Asynchronous motors;Pumps and fans in HVAC;
  • ARRA Compliant: N
  • Buy American Compliant: N
  • Catalog Number: ATV212HU22N4
  • Control: +/- 10 OF NOMINAL SLIP 0.2 TN TO TN
  • Country of Origin: FR
  • Currency: USD
  • Display: for DC bus energized 1 LED (red)
  • Display Type: Analog
  • Enclosure: OPEN IP20
  • Enclosure Type: IP20/IP21/IP41/Open
  • Environmental Conditions: -10-40 A°C WITHOUT)-40-50 A°C WITH DERATING FACTOR),CLASSES 3C1 IEC 60721-3-3-CLASSES 3S2 IEC 60721-3-3
  • EU RoHS Indicator: Y
  • Gross Volume Per Pack: 406.62
  • Gross Volume per Pack Metric: 6663.28
  • Gross Volume UOM: CI
  • Gross Volume UOM Metric: cm3
  • Gross Weight Per Pack: 4.3000 lb
  • Gross Weight per Pack Metric: 1.95
  • Gross Weight UOM Metric: kg
  • Harmonization Tariff Schedule Code: 8504404000
  • Height: 18.0000 in
  • Height [Metric]: 17.5000 cm
  • Input Voltage: 380...480 V - 15...10 %
  • Item Group: 22157
  • Length: 21.2000 in
  • Length [Metric]: 20.5000 cm
  • Material Composition Declaration: https://checkaproduct.se.com/DistantRequestDispatcher.aspx?action=export&pid=61737746&lang=en-us
  • Number Of Phases: 3
  • Power Rating: 103 W
  • Returnable: Y
  • Series: Altivar™ 212
  • Size: 107 MM,143 MM,150 MM in
  • Standard: IP21
  • Sub Brand: ATV212
  • Substitute Product Catalog Number: TCSMCNAM3M002P
  • Type: 3-Phase
  • UNSPSC: 39122001
  • UPC 11: 78590191594
  • UPC 12: 785901915942
  • Warranty Description: Contractual Warranty:18 months
  • Width [Metric]: 17.5000 cm
  • Stock Status: NORMALLY STOCKED
  • Brand: Schneider Electric
  • Manufacturer: Schneider Electric
  • Amperage Rating: 5.1 A
  • Depth: 5.91 in
  • Horsepower: 3 hp
  • Voltage Rating: 380 to 480 VAC
  • Width: 18.5000 in
QTY
  • Applications
  • Features
Asynchronous motors;Pumps and fans in HVAC;
VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES terminal 2.5-2.5 mm² / AWG 14;L1/R, L2/S, L3/T terminal 6-6 mm² / AWG 10;Voltage/frequency ratio, automatic IR compensation (U/f + automatic Uo);voltage/frequency ratio, 5 points;flux vector control without sensor, standard;voltage/frequency ratio - Energy Saving, quadratic U/f;voltage/frequency ratio, 2 points;Overheating protection drive;line supply undervoltage drive;against input phase loss drive;thermal protection motor;motor phase break motor;with PTC probes motor;thermal power stage drive;short-circuit between motor phases drive;input phase breaks drive;overcurrent between output phases and earth drive;overvoltages on the DC bus drive;break on the control circuit drive;against exceeding limit speed drive;line supply overvoltage and undervoltage drive;Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, <10 A overload and short-circuit protection;internal supply 24 V DC 21-27 V), <200 A overload and short-circuit protection
5.1 A at 380/460 VAC
Lower maintenance costs-reduce the mechanical stress on belts, piping and ductwork and eliminate valve or inlet guide vane maintenance
Reduced harmonics embedded reduced harmonic technology is equivalent to installing a 3% line reactor saving panel space and reducing component and wiring costs
Reduce installation costs embedded technology reduces input currents which allows a cost reduction in wire size, short circuit protection devices and enclosure size
Improve operating efficiency embedded technology reduces input currents which improves operating efficiency by 10% in many installations
Achieve 12 to 24 month payback for AC drives installed on typical pump or fan applications