Sentron™ 5SY6306-6 5SY Miniature Circuit Breaker, 400 VAC, 6 A, 5 kA Interrupt, 3 Poles, Thermal Magnetic Trip

Supplementary Protectors
944042 MFG #: 5SY6306-6
Siemens
92.83000 / ea
  • Actuator Type: Handle
  • Alternate Catalog Number: 5SY6306-6
  • Application: SUPPLEMENTARY PROTECTION
  • ARRA Compliant: C
  • Buy American Compliant: C
  • Catalog Number: 5SY6306-6
  • Connection: Identical wire screw connections on line and load side.
  • Connection Type: Line/Load/Screw
  • Country of Origin: DE
  • Currency: USD
  • Dimensions: 90 mm H x 54 mm W x 76 mm D
  • Enclosure Type: IP20/IP40
  • EU RoHS Indicator: C
  • Frame: 5SY6
  • Frequency Rating: 50 Hz
  • Gross Volume Per Pack: 27.97
  • Gross Volume UOM: in
  • Gross Weight Per Pack: 1.0410 lb
  • Gross Weight per Pack Metric: 0.47
  • Gross Weight UOM Metric: kg
  • Harmonization Tariff Schedule Code: 8536200020
  • Height: 3.31 in
  • Height [Metric]: 8.4074 cm
  • Length: 3.70 in
  • Length [Metric]: 9.4005 cm
  • Mounting Type: DIN Rail
  • Returnable: Y
  • Standard: UL 1077 and CSA C22.2 No. 235, IEC/EN 60898-1, IEC/EN 60947-2
  • Standards: ARRA CompliantBuy American Act CompliantRoHS CompliantCSA C22.2 No. 235IEC/EN 60898-1IEC/EN 60947-2CE MarkedCCC MarkedIMQ CertifiedUL 1077
  • Sub Brand: SENTRON
  • Temperature Rating: -25 to 55 °C
  • Trip Range: 40.68 to 52.2 A
  • Type: MINIATURE CIRCUIT BREAKER
  • UNSPSC: 39121601
  • UPC 11: 75455496124
  • UPC 12: 754554961248
  • Width: 2.28 in
  • Width [Metric]: 5.7988 cm
  • Wire Size: 14 to 4 AWG
  • Stock Status: NONSTOCK
  • Brand: Siemens
  • Manufacturer: Siemens
  • Amperage Rating: 6 A
  • Interrupt Rating: 6 kA
  • Trip Type: Thermal Magnetic
  • Voltage Rating: 480 VAC
  • Number Of Poles: 3
SIEMENS 5SY6306-6 UL1077 SUP. PROT 6KA 3P 6A B-TRIP
QTY
  • Applications
  • Features
SUPPLEMENTARY PROTECTION
Type B characteristic designed for European residential circuit protection. This characteristic can also be used for protection of computers and electronic equipment. Magnetic trip point - 3 to 5 times In rating. Thermal trip point - 1.13 to 1.45 protecto
Clear and visible conductor connection in front of the rear busbar facilitates controls
The conductor is easily inserted into the terminal thanks to the large and easily accessible wiring space
Double terminal chambers permit accommodation of two wires of different cross-sections
Quick and easy manual removal of miniature circuit breakers from the busbar assembly, for example if connections need to be changed
Time saving replacement of parts as busbars no longer need to be freed from adjacent devices
For the quick and easy mounting of auxiliary switches and fault signal contacts
Captive metal brackets on the additional components ensure the quick and easy mounting of devices on the miniature circuit breakers without the need for tools
Class B-trip
Type B characteristic designed for European residential circuit protection
This characteristic can also be used for protection of computers and electronic equipment
3 to 5 times magnetic trip point rating
1.13 to 1.45 thermal trip point protector rating