Siemens 3RV20214AA20 3RV2 Motor Protection Circuit Breaker, 690 VAC, 11 to 16 A, 2 kA Interrupt, 3 Poles, Magnetic Trip

Motor Protection Circuit Breakers
803078 MFG #: 3RV20214AA20
Siemens
165.94000 / ea
  • Alternate Catalog Number: 3RV2021-4AA20
  • Application: Used as Manual Motor Controller and in Group Installation
  • ARRA Compliant: C
  • Buy American Compliant: C
  • Catalog Number: 3RV20214AA20
  • Connection: spring-loaded terminals
  • Connection Type: Spring
  • Country of Origin: DE
  • Currency: USD
  • Dimensions: 119 mm H x 45 mm W x 97 mm D
  • Enclosure Type: IP20
  • Environmental Conditions: 80 -50 C
  • EU RoHS Indicator: C
  • Frame: S0
  • Frequency Rating: 50/60 Hz
  • Gross Volume Per Pack: 46.37
  • Gross Volume UOM: in
  • Gross Weight Per Pack: 0.8600 lb
  • Gross Weight per Pack Metric: 0.39
  • Gross Weight UOM Metric: kg
  • Harmonization Tariff Schedule Code: 8536304000
  • Height: 5.20 in
  • Height [Metric]: 13.2080 cm
  • Length: 4.35 in
  • Length [Metric]: 11.0490 cm
  • Mounting Type: DIN Rail/Snap-On/Threaded
  • Operating Temperature: 60 to -20 °C
  • Phase: 3
  • Power Rating: 11 kW
  • Returnable: Y
  • Standard: CE / UL / CSA / CCC
  • Standards: CCC CertifiedCSA CertifiedUL ListedEAC ApprovedEX ATEXIECEx CertifiedCE CertifiedVDE ApprovedRoHS CompliantABS ApprovedBureau Veritas CertifiedLloyd's RegisteredPRS CertifiedRINA CertifiedRMRS ApprovedDNV-GL ApprovedEN 60715
  • Sub Brand: Sirius
  • Temperature Rating: -20 to 60 °C
  • Trip Range: 10 to 16 A, 208 A
  • Type: Type 3RV2
  • UNSPSC: 39121601
  • UPC 11: 66264392429
  • UPC 12: 662643924299
  • Width: 2.05 in
  • Width [Metric]: 5.2070 cm
  • Wire Size: 18 to 8 AWG
  • Stock Status: NONSTOCK
  • Brand: Siemens
  • Manufacturer: Siemens
  • Amperage Rating: 16 A
  • Interrupt Rating: 4 kA
  • Trip Type: Thermomagnetic
  • Voltage Rating: 690 VAC
  • Number Of Poles: 3
Siemens 3RV20214AA20 MSP S0 11-16A SPRING
QTY
  • Applications
  • Features
Used as Manual Motor Controller and in Group Installation
MSP?s are UL approved as Self Protected Combination Motor Controllers
Minimization of energy losses through optimization of the bimetal trip units
Reduction of inherent power loss
Less heating of the control cabinet
Smaller control cabinet air conditioners can be used
3RV2 motor starter protectors/circuit breakers are suitable for operation in IT systems (IT networks)
4000 W at 230 VAC, 7500 W at 400 VAC, 7500 W at 500 VAC, 11000 W at 690 VAC
100 kA at 240 VAC, 55 kA at 400 VAC, 10 kA at 500 VAC, 4 kA at 690 VAC
10 to 16 A thermal overload release, 208 A instantaneous overcurrent release
Without auxiliary switch