Siemens 3RV2 Motor Protection Circuit Breaker, 690 VAC, 2.8 to 4 A, 4 kA Interrupt, 3 Poles, Magnetic Trip

Motor Protection Circuit Breakers
1033662 MFG #: 3RV21111EA10
Siemens
208.80000 / ea
  • Alternate Catalog Number: 3RV2111-1EA10
  • Application: MSP with overload relay function
  • ARRA Compliant: C
  • Buy American Compliant: C
  • Catalog Number: 3RV21111EA10
  • Connection: screw-type terminals
  • Connection Type: Screw
  • Country of Origin: DE
  • Currency: USD
  • Dimensions: 97 mm H x 65 mm W x 96 mm D
  • Enclosure Type: IP20
  • Environmental Conditions: 80 -50 C
  • EU RoHS Indicator: C
  • Frame: S00
  • Frequency Rating: 50 to 60 Hz
  • Gross Volume Per Pack: 49.61
  • Gross Volume UOM: in
  • Gross Weight Per Pack: 0.8360 lb
  • Gross Weight per Pack Metric: 0.38
  • Gross Weight UOM Metric: kg
  • Harmonization Tariff Schedule Code: 8536308000
  • Height: 4.10 in
  • Height [Metric]: 10.4140 cm
  • Length: 4.26 in
  • Length [Metric]: 10.8204 cm
  • Mounting Type: DIN Rail
  • Operating Temperature: 60 to -20 °C
  • Phase: 3 pH
  • Power Rating: 3 kW
  • Replaced Catalog Number: 3RV1121-1EA10
  • Returnable: Y
  • Series: 3RV2
  • Standard: CE / UL / CSA / CCC
  • Standards: CSA CertifiedCCC CertifiedCE CertifiedIEC CertifiedUL Listed
  • Sub Brand: Sirius
  • Temperature Rating: -20 to 60 °C
  • Trip Range: 52 A
  • Type: 3RV2 circuit breaker
  • UNSPSC: 39121601
  • UPC 11: 66264392308
  • UPC 12: 662643923087
  • Width: 2.84 in
  • Width [Metric]: 7.2136 cm
  • Wire Size: 18 to 14 AWG
  • Stock Status: NONSTOCK
  • Brand: Siemens
  • Manufacturer: Siemens
  • Amperage Rating: 2.8 to 4 A
  • Interrupt Rating: 4 kA
  • Trip Type: Magnetic
  • Voltage Rating: 690 VAC
  • Number Of Poles: 3
The SIRIUS 3RV2 motor starter protectors/circuit breakers are compact, current limiting motor starter protectors/circuit breakers which are optimized for load feeders. The motor starter protectors/circuit breakers are used for switching and protecting three-phase motors of up to 55/45 kW at 400 VAC and for other loads with rated currents of up to 100 A.
QTY
  • Applications
  • Features
MSP with overload relay function
Overload relay function, class 10, automatic reset
Class 10 trip
Reduction of inherent power loss
Less heating of the control cabinet
Smaller control cabinet air conditioners can be used
3RV2 motor starter protectors/circuit breakers are suitable for operation in IT systems (IT networks)
750 W at 230 VAC, 1500 W at 400 VAC, 2200 W at 500 VAC, 3000 W at 690 VAC
100 kA at 240 VAC, 100 kA at 400 VAC, 100 kA at 500 VAC, 6 kA at 690 VAC
2.8 to 4 A thermal overload release, 52 A instantaneous overcurrent release
Without auxiliary switch