Schneider Electric GB2DB12, 415 VAC, 6 A
Motor Circuit Protectors
1309387
MFG #: GB2DB12
Square D™
114.60000
/ ea
- Alternate Catalog Number: GB2DB12
- Application: For protection of DC loads up to 6A/48V DC-13 with a breaking capacity Icu 1, For the protection of industrial equipment control circuits, For 8000 cycles
- ARRA Compliant: N
- Buy American Compliant: N
- Catalog Number: GB2DB12
- Country of Origin: FR
- Currency: USD
- EU RoHS Indicator: Y
- Gross Volume Per Pack: 42.00
- Gross Volume per Pack Metric: 688.25
- Gross Volume UOM: CI
- Gross Volume UOM Metric: cm3
- Gross Weight Per Pack: 1.0400 lb
- Gross Weight per Pack Metric: 111.00
- Gross Weight UOM Metric: g
- Harmonization Tariff Schedule Code: 8536200020
- Height: 3.1000 in
- Height [Metric]: 3.1000 cm
- Item Group: 22631
- Length: 7.5000 in
- Length [Metric]: 7.5000 cm
- Material Composition Declaration: https://checkaproduct.se.com/DistantRequestDispatcher.aspx?action=export&pid=6969198&lang=en-us
- Returnable: N
- UNSPSC: 39121633
- Warranty Description: Contractual Warranty:18 months
- Width: 7.4000 in
- Width [Metric]: 7.4000 cm
- Stock Status: NONSTOCK
- Brand: Square D™
- Manufacturer: Schneider Electric
Schneider Electric GB2DB12, 415 VAC, 6 A, 50/60 Hz Frequency, connector 1 0.00 to 0.01 sq. in. (0.75 to 6 sq. mm) solid without cable end/connector 2 0.00 to 0.01 sq. in. (0.75 to 4 sq. mm) solid without cable end/connector 1 0.00 to 0.01 sq. in. (0.75 to 4 sq. mm) flexible with cable end/connector 2 0.00 to 0.00 sq. in. (0.75 to 2.5 sq. mm) flexible with cable end Connection, IP20 Enclosure, -4 to 140 deg F, 2.91 in H x 1.18 in W x 2.76 in D Dimensions
- Applications
- Features
For protection of DC loads up to 6A/48V DC-13 with a breaking capacity Icu 1, For the protection of industrial equipment control circuits, For 8000 cycles |
TeSys GB2 thermal-magnetic circuit breakers are available in various ratings and with different breaking capacities |
Compliance with standards: IEC 947-1, 947-2 |
1-pole + neutral (GB2 CD) |
2-pole (GB2 DB) |
Magnetic tripping threshold set between 12 to 16 In (withstands current peaks generated by many industrial components.) |
2 ratings available: 0.5 and 1 A |
1-pole version |
Magnetic tripping threshold set between 5 and 7 In |
15 mm wide for 1-pole |
AC/DC network type |
AC/DC network type |
75 % 110 V AC 50/60 Hz IEC 60947-275 % 230/240 V AC 50/60 Hz IEC 60947-275 % 400/415 V AC 50/60 Hz IEC 60947-2 ics rated service short-circuit breaking capacity |
83 A magnetic tripping current |
HorizontalVertical mounting position |
4 kV IEC 60947-2 uimp rated impulse withstand voltage |
8000 cycles mechanical durability |
Shocks 22 Gn for 20 ms IEC 60068-2-27Vibrations 5 Gn, 5 to 110 Hz IEC 60068-2-6 mechanical robustness |
4 9 mm pitches |
TC protective treatment |
1760 deg F (960 deg C) IEC 60695-2-1 fire resistance |