• Applications
  • Features
For most sophisticated control and protection requirements with display
Manual or automatic reset;monitoring function, indication of main motor parameters;overload, no-load running;protection function alarm;protection against overload and short-circuit;protection against phase failure and phase imbalance;earth fault protection;log function;differentiation of thermal overload and magnetic fault;RS485 multidrop RJ45 front panel Modbus RTU 19200 bit/s;2 lines of 12 characters LCD - English +/- 5 % 1 % of Ir;2 lines of 12 characters LCD - French +/- 5 % 1 % of Ir;2 lines of 12 characters LCD - German +/- 5 % 1 % of Ir;2 lines of 12 characters LCD - Italian +/- 5 % 1 % of Ir;2 lines of 12 characters LCD - Spanish +/- 5 % 1 % of Ir;English factory setting;English, French, German, Italian, Spanish settable
IP20 front panel and wired terminals and IP40 front panel outside connection zone
15 kW at 400 to 440 VAC 15 kW at 500 VAC/ 8.5 kW at 690 VAC at 50/60 Hz
8 to 32 A thermal protection adjustment range
Plug-in mounting
Front side mounting location
20 to 28 VDC control circuit voltage limits
150/200/70/75 mA at 24 VDC current consumption
35/65/75 msec operating time
600/690 VAC rated insulation voltage
0.8/1.7/1.8 W heat dissipation
0.8/1.7/1.8 W heat dissipation
-40 to 85 deg C storage temperature
1202/1760 deg F fire resistance
10/15 gn shock resistance
2/4 gn vibration resistance
8 kV resistance to electrostatic discharge
10 V immunity to radio electric fields