Appleton® AEBB12260C AE Series Explosionproof Enclosure With Circuit Breaker, 20.5 in L x 11 in W x 8.97 in D, NEMA 4/4X/7CD/9EFG
Explosion Proof Circuit Breakers
844286
MFG #: AEBB12260C
Appleton™
3258.48000
/ ea
- Actuator Type: Handle
- ARRA Compliant: C
- Buy American Compliant: Y
- Catalog Number: AEBB12260C
- Color: Gray
- Connection Type: Lug
- Country of Origin: US
- Currency: USD
- Dimensions: 20.5 H x 11 in W x 8.97 in D
- Enclosure Type: NEMA 4/4X
- EU RoHS Indicator: N
- Finish: Epoxy Powder Coated
- Frame: 100 A
- Gross Weight Per Pack: 1 lb
- Material: Copper Free Aluminum
- Number Of Poles: 2
- Series: AE Series
- Standards: ARRA CompliantBuy American Act CompliantUL 1203UL File No. E84577CSA C22.2 No. 0C22.2 No. 4C22.2 No. 5C22.2 No. 25C22.2 No. 30NEC CompliantCEC Class I Div 1 and 2, Groups B, C, D, Class II, Div 1 and 2, Groups E, F, G, Class III
- Type: Bolted Enclosure Dust-Ignitionproof Explosionproof Watertight
- UNSPSC: 39121601
- UPC 11: 78138185714
- UPC 12: 781381857147
- Stock Status: NONSTOCK
- Brand: Appleton™
- Manufacturer: Appleton
- Amperage Rating: 60 A
- Interrupt Rating: 18 kA
- Trip Type: Non-Interchangeable
- Voltage Rating: 240 VAC
- Features
With 60 A, 18 kA, 2P, 14 - 1/0 AWG, 100 - 150 A frame, non-interchangeable Cutler Hammer circuit breaker |
Constructional feature explosion proof, dust-Ignition proof, watertight |
Ground lug package and instructions for termination of ground wire included |
External operating handle with stops for limiting handle travel |
Breaker operators can be locked in the On or Off position |
External flange maximizes internal space |
Standard outlets top and bottom for line and load wiring |
Plugged 1/2 in outlets top and bottom for breather and drain |
Breakers mounted on removable galvanized steel pan |
O-ring gasket insures watertight integrity |
Copperfree (4/10 of 1% max.) aluminum body and cover with epoxy powder coat finish, stainless steel captive Quad-Lead® cover bolts, hinges, breaker and operator shafts, neoprene O-ring |
Dead end hub location |
2 in hub |
18 kA at 240 VAC, 14 kA at 480 VAC |
240 VAC/125/250 VDC |